Current Limit Starting - WEG SSW-07 Manual Del Usuario

Ocultar thumbs Ver también para SSW-07:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Chapter 5 - prOGraMMING INFOrMatION aND SUGGeStIONS
5.1.2 Current Limit
Starting
38
1) To start with a current limitation it is necessary to start with a load.
Initial test without load can be done with a voltage ramp;
2) Set the acceleration time with the necessary starting time, initially
with short times, 20 to 25 seconds. This time will be used as the
stall time in case the motor does not start;
3) Set the current limit according to the conditions that your electric
installation allows, as well as to the values that supply enough
torque to start the motor. It can initially be programmed with
values between 2x and 3x the nominal current of the motor (ln
of the motor).
I(A)
Start
I Limitation
Maximum Time
0
Current Limitation
Enable
Figure 5.4 - Current limit starting
NOTES!
 If the current limit is not reached during the start, the motor will
start immediately;
 Very low Current Limit values do not provide sufficient torque to
start the motor. Always keep the motor rotating once it is started.
 For loads that need a higher initial starting torque, the Kick Start
function can be used;
 If faults occur during the start, check all the connections from the
Soft-Starter to the supply network, motor connections, supply
network voltage levels, fuses and circuit breakers.
I Nominal
Disable
t(s)

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ssw 07 serie

Tabla de contenido