Control And Signal Connections; Recommended Set-Ups - WEG SSW-07 Manual Del Usuario

Ocultar thumbs Ver también para SSW-07:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Chapter 3 - INStaLLatION aND CONNeCtION
3.2.7 Control
and Signal
Connections
Terminal
A1
Electronics Supply
A2
Grounding
Terminal
DI1
Starts/Stops Motor
DI2
Fault reset
DI3
Fault reset
13
Relay 1 output - Operation
14/23
Relay common point
24
Relay 2 output - Full voltage
3.3 RECOMMENDED
SET-UPS
22
EMI - Electronic Interference
The Soft-Starter SSW-07 is developed to be used in industrial
systems (Class A) according to Standard EN60947-4-2.
It's necessary to have a distance of 0.25 m (10 in) between the
Soft- Starter SSW-07 control cables and motor cables.
Example: PLC wiring, temperature controllers, thermocouple cables,
etc.
Grounding of the Motor frame
Always ground the motor frame. The Soft-Starter SSW-07 output
wiring to the motor must be installed separately from the input wiring
as well as from the control and signal wiring.
The control connections (digital inputs and relay outputs) are made
through the terminals (refer to figure 3.9).
Description
Voltage: 110 to 240 Vac (-15 % to +10 %)
(models from 17 A to 200 A)
110 to 130 Vac or 208 to 240 Vac
(-15 % to 10 %) (models from 255 A
to 412 A).
Only for the 255 to 412 A models
Factory Default
3 isolated digital inputs
Voltage: 110 to 240 Vac (-15 % to +10 %)
Current: 2 mA Max.
Contact capacity:
Voltage: 250 Vac
Current: 1 A
table 3.9 - Description of the control connector pins
Figure 3.9 - Control terminals of the Soft-Starter SSW-07
Some recommended set-ups are shown here and they can be
completely or partly used.
The main warning notes for all the recommended set-ups are
shown below and are described in the schemes by their respective
numbers.
Specifications
Specifications
Torque Nm
(in lb)
0.5 (4.5)

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Ssw 07 serie

Tabla de contenido