Hitachi IVX-ES Serie Manual De Instalación Y Funcionamiento página 41

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 43
Code
Category
No.
11
12
Sensor on
13
Indoor Unit
14
19
20
Sensor on
22
Outdoor Unit
24
31
35
System
38
41
Pressure
42
47
48
51
53
Inverter
54
55
57
Outdoor Fan
59
Inverter
Indoor unit No.
b1
setting
EE
Compressor
PMML0197_r0_04-10.indb 41
INSTALLATION AND OPERATION MANUAL
Content of Abnormality
Inlet Air Thermistor
Outlet Air Thermistor
Freeze Protection Thermistor
Gas Piping Thermistor
Tripping of Protection Device for Fan Motor
Compressor Thermistor
Outdoor Air Thermistor
Evaporating Thermistor
Incorrect Setting of Outdoor and Indoor Unit
Incorrect Setting in Indoor Unit No.
Abnormality of Protective Circuit in Outdoor Unit
Overload Cooling
(Possibility of high pressure device activation)
Overload Heating
(Possibility of high pressure device activation)
Activation of Low Pressure Decrease Protection
Device
Activation of overload protection
Abnormality of Current Sensor for Inverter
Protection Activation of Transistor Module
Inverter Fin Temperature Increase
Inverter Module Abnormality
Fan Motor Abnormality
Thermistor of Inverter Fin Abnormality (for
Inverter Fin Temperature)
Incorrect unit No. Setting
Compressor Protection Alarm
Leading Cause
Failure of Thermistor, Sensor, Connection.
Failure of Fan Motor
Failure of Thermistor, Sensor, Connection
Incorrect Setting of Capacity Code.
Duplication of Indoor Unit number, Nº of Indoor unit over
specifications.
Failure of Indoor Unit PCB. Incorrect wiring. Connection to PCB in
Indoor Unit.
O.U. Pipe Thermistor Temp. is Higher than 55ºC
and the Comp. Top Temp. is Higher than 95ºC
when O.U. Protection Device is activated.
I.U. Freeze Protection Thermistor Temp. is Higher than 55ºC and the
Comp. Top Temp. is Higher than 95ºC when O.U. Protection Device
is activated.
Stoppage by Excessively Decrease of evaporating Temperature
(Te < -35ºC) is activated 3 times in one hour, Locked Motor in Heating
Operation.
Overcurrent in Inverter Module.
Failure of Control PCB, Inverter Module.
Transistor Module Abnormality.
Failure of Compressor, clogging of Heat Exchanger.
Abnormal Inverter Fin Thermistor.
Clogging of Heat Exchanger
Abnormal Outdoor Fan
Failure of Inverter Module.
Disconnected wire of Incorrect wiring between Control PCB and
Inverter PCB.
Incorrect Wiring or Fan Motor Abnormality
Loose connector, Disconnnected wire short circuit
Over 64 indoor units setting by No. or indoor unit address.
Failure of Compressor.
41