12 DRAIN PIPING
12.1. DRAIN DISCHARGING BOSS
When the base of the outdoor unit is temporarily utilized as a drain
receiver and the drain water in it is discharged, this drain boss is utilized
to connect the drain piping.
Model
DBS-26
Connecting procedure
1. Insert the rubber cap into the drain boss up to the extruded
portions
2. Insert the boss into the unit base and turn approximately 40
degree counterclockwise.
3. Size of the drain boss is 32 mm (O.D.)
4. A drain pipe should be field-supplied
13 ELECTRICAL WIRING
13.1. GENERAL CHECK
1. Ensure that the field-supplied electrical components (mains power
switches, circuit breakers, wires, connectors and wire terminals) have
been properly selected according to the electrical data indicated.
Make sure that they comply with national and regional electrical
codes.
2 Following the Council Directive 2004/108/EC(89/336/EEC), relating
to electromagnetic compatibility, next table indicates:
Maximum permissible system impedance Z
the user's supply, in accordance with EN61000-3-11
MODEL
RAS-3HVRNME
RAS-4HVRNM1E/4HVRNS1E
RAS-5HVRNM1E/5HVRNS1E
RAS-6HVRNM1E/6HVRNS1E
3. Harmonics situation of each model regarding IEC 61000-3-2 and IEC
61000-3-12 is as follows:
MODELS SITUATION REGARDING
IEC 61000-3-2 AND IEC 61000-3-12
Ssc "xx"
Equipment complying with IEC 61000-3-2
(*)
(professional use
)
4. Check to ensure that the power supply voltage is within +/-10% of the
rated voltage.
5. Check to ensure that power supply has an impedance low enough to
warranty not reduce the starting voltage more than 85% of the rated
voltage.
6. Check to ensure that the ground wire is connected.
PMML0197_r0_04-10.indb 31
INSTALLATION AND OPERATION MANUAL
Applicable Model
H(V)RNM(1)E/HVRNS1E
at the interface point of
max
Zmax (Ω)
-
0.41/0.31
0.29/0.29
0.29/0.29
Ssc "xx"
MODELS
(KVA)
(*)
RAS-4HRNM1E
(*)
-
RAS-5HRNM1E
(*)
RAS-6HRNM1E
RAS-3HVRNME
RAS-4HVRN(S/M)1E
-
RAS-5HVRN(S/M)1E
RAS-6HVRN(S/M)1E
NOTE:
Do not use this drain boss set in a cold area, because the drain
water may freeze.This drain boss is not sufficient to collect all
the drain water. If collecting drain water is completely required,
provide a drain-pan that is bigger than the unit base and install it
under the unit with drainage.
Drain pipe
Drain pipe
Extruded portion
Drain Boss
Rubber cap
7. Connect a fuse of specified capacity.
WARNING:
Check to ensure that screws for terminal block are tightly
tightened.
CAUTION:
Check to ensure that the indoor fan and the outdoor fan have
stopped before electrical wiring work or periodical check is
performed.
Protect the wires, drain pipe, electrical parts, from rats or other
small animals. If not protected, rats may damage unprotected
parts, and at the worst, a fire will occur.
Wrap the accessory packing around the wires, and plug the wiring
connection hole with the seal material to protect the product from
any condensed water and insects.
Tightly secure the wires with the cord clamp inside the indoor unit.
Lead the wires through the knockout hole in the side cover when
using conduit.
Secure the cable of the remote control switch with the cord clamp
inside the electrical box.
Electrical wiring must comply with national and local codes.
Contact your local authority in regards to standards, rules,
regulations, etc.
Check that the ground wire is securely connected.
Connect a fuse of specified capacity.
DANGER:
Do not connect of adjust any wiring or connections unless the
main power switch is OFF.
Check that the earth wire is securely connected, tagged and
locked in accordance with national and local codes.
NOTE:
Check and test to ensure that if there is more than one source of
power supply, that all are turned OFF.
31
Drain hole of
Base
08/07/2010 9:20:50