Descargar Imprimir esta página

Vaillant sensoHOME VRT 380f/2 Manual De Uso E Instalación página 13

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 53
MENU → SETTINGS → Installer level → Installation configuration
→ Control:
→ OT constant heating: °C
→ Desired preheating temp.:
→ Heat generator 1
→ Status:
→ Current flow temperature: °C
→ Circuit 1
→ Status:
→ Target flow temperature: °C
→ OT switch-off threshold: °C Enter the upper limit for the outdoor temperature. If the
→ Heat curve:
→ Min. target flow temperat-
ure:°C
→ Max. target flow temperat-
ure:°C
→ Set-back mode:
0020323648_01 Operating and installation instructions
R.temp.
It is controlled via the room temperature.
contr
Weath.-
It is controlled via the outdoor temperature
comp.
as soon as an outdoor temperature sensor is
connected.
If the outdoor temperature falls below the set temperature
value, the Heat curve: is used to regulate to a room tem-
perature of 20 °C outside of the time periods.
OT ≤ set temperature value: No night set-back or total shut-
down
Factory setting: Off
This is where you can select the desired pre-heating time
temperature in order to activate the heating before the
heating programme first starts. The aim is to reach the
room temperature at the desired time. The system auto-
matically calculates the required prerun time (max. 4 hrs)
based on prior experience, the current room temperature
and the time remaining until the programme changes.
Factory setting: Off
outdoor temperature rises above the set value, the control
deactivates heating mode.
The heat curve (→ section "Product description") is the de-
pendence of the flow temperature on the outdoor temperat-
ure for the desired temperature (target room temperature).
Enter the lower limit for the target flow temperature. The
control compares the set value with the calculated target
flow temperature, and regulates to the larger of these val-
ues.
Enter the upper limit for the target flow temperature. The
control compares the set value with the calculated target
flow temperature, and regulates to the smaller of these val-
ues.
13

Publicidad

loading

Este manual también es adecuado para:

Vrt 380f/2