MENU → SETTINGS → Installer level → Installation configuration
→ Zone activated:
→ Zone assignment:
→ Zone valve status:
→ DHW
→ Cylinder:
→ Target flow temperature: °C
→ Circulation pump:
→ Anti-legio. day:
→ Anti-legio. time:
→ Radio link
→ Sys. control reception
strength:
→ OT sensor reception
strength:
→ Screed drying profile
0020323648_01 Operating and installation instructions
Deactivate zones that are not required. All existing zones
appear in the display.
Assign the control to the selected zone. The control must
be installed in the selected zone. The control system also
uses the room temperature sensor for the assigned unit. If
no zone has been assigned to the control, the Room temp.
mod.: function is ineffective.
If there is an existing domestic hot water cylinder, the Act-
ive setting must be selected.
Define the days on which you want the anti-legionella func-
tion to run. On these days, the water temperature is in-
creased to above 60 °C. The circulation pump is activated.
The function ends after 120 minutes at the latest.
If the Absence function is activated, the anti-legionella
function is not carried out. As soon as the Absence func-
tion ends, the anti-legionella function is carried out.
Define the time at which you want the anti-legionella func-
tion to run.
Read the reception strength between the radio receiver unit
and outdoor temperature sensor.
– 4: The radio link is within the acceptable range. If the
reception strength is < 4, the radio link is not stable.
– 10: The radio link is highly stable.
Read the reception strength between the radio receiver unit
and outdoor temperature sensor.
– 4: The radio link is within the acceptable range. If the
reception strength is < 4, the radio link is not stable.
– 10: The radio link is highly stable.
Setting target flow temperature per day in accordance with
the construction regulations
15