MSW Motor Technics MSW-PLT-W24 Manual De Instrucciones página 91

Publicidad

A - Exhaust terminal
B - Fresh air
C - Mechanical air supply inlet
The clearance to a door, window or cavity must be at least:
- 1.5' (458 mm) below;
- 1.5' (458 mm) horizontally;
- 9'' (230 mm) above.
The clearance to fresh air intake for combustion of the pellet stove or any other appliance,
or the non-mechanical air supply inlet to the building must be at least 4' (1.2 m).
The clearance to a mechanical air supply inlet to the building must be at least 8' (2.5 m).
The exhaust termination location (Fig. 20) must be at least:
• 1' (305 mm) above the ground level. Attention : the minimum vertical rise shall
always be not less than 5' (1.5 m). A flue at 1'above ground is not enfant safe: we
strongly recommend that the exhaust termination of flue be raised another 4' to
avoid injury.
• 7' (2.1 m) from a public walkway, but attention to where the vent shall end its
course, as it is not to be in between or serve two family dwellings and/or directly
above sidewalks or paved driveways;
• 1' (305mm) from the wall penetration point;
• 3' (915 mm) from a gas meter/regulator assembly;
• 3' (915 mm) from any adjacent combustibles such as: adjacent buildings, fences,
protruding parts of the structure, roof eaves or overhangs, plants, shrubs, etc.
-The exhaust gases from the combustion of pellets fuel may dirty the outside of the walls.