The product must be installed and used in compliance with the manufacturer's instructions
and national standards as well as local regulations.
-When a flue pipe passes through a wall or a ceiling, special installation methods must be
applied (protection, thermal insulation, distances from heat-sensitive materials, etc.) See
the paragraph from "Interior vent installation" to "Short rise installation - wall outlet".
• It is also recommended that all elements made of combustible or inflammable material,
such as beams, wooden furniture, curtaining, flammable liquids, etc. be kept outside the
heat radiation range of the stove and at a distance of at least 32"/ 80 cm from the heating
block.
• For other information, see the paragraph from "Minimum safety distances" to "Venting:
termination requirements".
• The flue pipe, chimney stack, chimney and fresh air intake must always be free of
obstructions, clean and checked periodically, that is, at least twice during the seasonal
period from the lighting of the stove and during its use. When the stove has not been used
for some time it is advisable to carry out the checks mentioned above. For further
information, consult a chimney sweep.
• Only use recommended fuels (See section "Fuel").
Mobile home installation
The stove has been tested and listed for mobile home installations.
Unit must be installed in accordance with the: Manufactured Home and Safety Standard
EN14785:2006, CFR
In addition to all previously detailed requirements, mobile home installations must observe
the following:
- Permanently bolt the stove to the floor. Use 4 screws [A] through the 4 holes placed at left
and right side in the base plate as shown in figure 21.
- Electrically ground the stove to the metal chassis of the home using a number 8 or larger
copper wire [B].
- Maintain an effective vapor barrier at location where PL vent exits the structure.
- Floor protection and clearances requirement must be followed precisely as shown in the
previous paragraphs.
- PL Vent must be used for exhaust venting. (Single wall vent is not allowed). Follow PL Vent
manufacturer's installation directions and observe all listed clearances to combustibles.
- Check any other local buildings codes or other codes that may apply.