Installation Dx-coil controller (Electrical wiring, DN setting)
WARNING
1. Using the specified wires, ensure to connect the wires,
and fix wires securely so that the external tension to
the wires do not affect the connecting part of the
terminals. Incomplete connection or fixation may
cause a fire, etc.
2. Be sure to connect earth wire (grounding work).
Incomplete grounding cause an electric shock.
Do not connect ground wires to gas pipes, water
pipes, lightning rods or ground wires for telephone
wires.
3. Appliance shall be installed in accordance with
national wiring regulations.
Capacity shortage of power circuit or incomplete
installation may cause an electric shock or a fre.
4. For full disconnection under overvoltage category lll
Conditios must be incorporated in the fixed wiring
according to national wiring rules.
REQUIREMENT
• For power supply wiring, strictly conform to the Local
Regulation for each country.
• For wiring of power supply of the outdoor units, follow
the Installation Manual of each outdoor unit.
• Perform the electric wiring so that it does not come in
to contact with the high-temperature part of the pipe.
The coating may melt in an accident.
• After connecting wires to the terminal blocks, provide
a trap and fix the wires with the cord clamp.
• Run the refrigerant piping and control wiring line in
the same line.
• Do not turn on the power of the indoor unit until
vacuuming of the refrigerant pipes completes.
CAUTION
• If incorrect / incomplete wiring is carried out, it will
cause an electrical fire or smoke.
• Be sure to install an earth leakage breaker that is
not tripped by shock waves.
If an earth leakage breaker is not installed, an
electric shock may be caused.
• Be sure to use the cord clamps attached to the
product.
• Do not damage or scratch the conductive core and
inner insulator of power and inter-connecting wires
when peeling them.
• Use the power cord and inter-connecting wire of
specified thickness, type and protective devices
required.
• Do not connect 208 - 230 V power to the terminal
blocks (Uv (U1), Uv (U2), A, B, etc) for control wiring
(otherwise the system will fail).
Power supply wire and communication
wires specifcations
Power supply wire and communication wires are
procured locally. For the power supply specifications,
follow to the table below. If capacity is little, it is
dengerous because overheat or burnout may be caused.
For specifications of the power capacity of the
outdoor unit and the power supply wires, refer to the
Installation Manual attached to the outdoor unit.
Cable size must be calculated for site condition and
correct glands fitted.
All cables should be in conduit or armored cables
correctly glanced.
This has to be done by the site installer.
Dx-coil controller power supply
• For the power supply of the Dx-coil controller, prepare
the exclusive power supply separated from that of the
outdoor unit.
• Arrange the power supply, earth leakage breaker and
main switch of the Dx-coil controller connected to the
same outdoor unit so that they are commonly used.
• Power supply wire specification: Cable 3-Core,
AWG 12, in conformity with Design 60245 IEC 57.
Power supply
Power supply
Power supply switch / Earth leakage breaker or power
supply wirings / fuse rating for Dx-coil controllers should
be selected by the accumulated total current values of the
Dx-coil controllers.
Power supply wiring
(power supply and earth)
Current consumption
Control wiring, Central controller wiring
• 2-core with polarity wires are used for the Control
wiring between indoor and outdoor unit and Central
controller wiring.
• To prevent noise trouble, use 2-core shield wire.
– 19 –
208 - 230 V ~, 60 Hz
Below
0.9 in²
164' (50 m)
(2.5 mm²)