• For TA and TF type, the set temperature can be changed according to the 0 - 10 V input of AI3.
• In the set temperature with the remote controller and this control, the post-setting is prioritized.
• The set temperature can be changed only for cooling and heating operations.
• To use this control, set DN [4A9] = 1.
TA type
10.00
84°F (29°C) / 84°F (29°C)
9.70
82°F (28°C) / 82°F (28°C)
8.95
81°F (27°C) / 81°F (27°C)
8.20
79°F (26°C) / 79°F (26°C)
7.45
77°F (25°C) / 77°F (25°C)
6.70
75°F (24°C) / 75°F (24°C)
5.95
73°F (23°C) / 73°F (23°C)
5.20
72°F (22°C) / 72°F (22°C)
4.45
70°F (21°C) / 70°F (21°C)
3.70
68°F (20°C) / 68°F (20°C)
2.95
66°F (19°C) / 66°F (19°C)
2.20
64°F (18°C) / 64°F (18°C)
1.45
64°F (18°C) / 64°F (18°C)
0.70
0.00
Terminal AO1 / AO1: FAN speed 0 - 10 V output
• Each FAN speed is output at 0 - 10 V.
• The ripple voltage of 0 - 10 V is less than ± 30 mV of the
set voltage. Connect equipment that is not affected by
this ripple voltage.
• The output voltage can be changed by DN setting [4A4]
to [4A6].
* Terminal AO2 / AO2 cannot be used.
CAUTION
The impedance of the device that receives the 0 - 10 V output signal shall be 10 kΩ or more.
TCB-IFDMR01UP-UL
Shield wire MAX. 656'2" (200 m)
AO1
Output
0 - 10 V
AO1
Set temp
(V)
Heating / Cooling
9.50
8.75
8.00
7.25
6.50
5.75
5.00
4.25
3.50
2.75
2.00
1.25
0.50
Locally procured
0 - 10 V Signal (+)
GND (-)
TF type
10.00
86°F (30°C) / 77°F (25°C)
9.70
84°F (29°C) / 75°F (24°C)
8.95
82°F (28°C) / 73°F (23°C)
8.20
81°F (27°C) / 72°F (22°C)
7.45
79°F (26°C) / 70°F (21°C)
6.70
77°F (25°C) / 68°F (20°C)
5.95
75°F (24°C) / 66°F (19°C)
5.20
73°F (23°C) / 64°F (18°C)
4.45
72°F (22°C) / 63°F (17°C)
3.70
70°F (21°C) / 61°F (16°C)
2.95
68°F (20°C) / 59°F (15°C)
2.20
66°F (19°C) / 57°F (14°C)
1.45
64°F (18°C) / 55°F (13°C)
0.70
0.00
FAN
Output
speed
(Def)
HH
9 V
4A4 (0009)
H
6 V
4A5 (0006)
L
2 V
4A6 (0002)
STOP
0 V
– 31 –
Set temp
Heating / Cooling
Initial
Applicable range
(Def)
8 V (0008) - 10 V (0010)
4 V (0004) - 7 V (0007)
1 V (0001) - 3 V (0003)
-
-
(V)
9.50
8.75
8.00
7.25
6.50
5.75
5.00
4.25
3.50
2.75
2.00
1.25
0.50