38
Mounting 7820658/06 EN
5.4.9 Wiring DI 16-220 V digital inputs
If the device has DI 16-220 V connections, proceed as follows:
Check which version you have by looking at the connection terminal desig-
i
nation on the rear of the device.
1. Feed the wires into the terminal of the DI 16-220 V plug in accordance with
the connection diagram [►Section 8.14, Page 59] and fasten them using a
screwdriver.
2. Plug the connector into the respective slot and screw it into place.
5.4.10 Wiring digital outputs DO
Figure 37: Block diagram for digital outputs
1. Feed the wires into the terminal of the plug connection diagram and fasten
them using a screwdriver.
2. Plug the connector into the respective slot and screw it into place.
5.4.11 Wiring resistor contact series
Connect the resistor contact series to the COM X6 and AI 4 interfaces in accor-
dance with the connection diagram [►Section 8.14, Page 59].
5.4.12 Power supply and grounding
5.4.12.1 Connecting the power supply
You may only connect the device to circuits with an external overcurrent pro-
tective device and an all-pole isolating device, allowing the equipment to be
fully de-energized if required (service, maintenance etc.).
Suitable equipment includes isolating devices in accordance with IEC 60947-1
and IEC 60947-3 (e.g. circuit breakers). Observe the properties of the relevant
circuits (voltage, maximum currents) when selecting the circuit breaker type. In
addition, observe the following:
–
It must be easy for the operator to access the isolating device
–
The isolating device must be labeled for the device and the circuits to be iso-
lated
–
The isolating device may not be a part of the power line
–
The isolating device may not interrupt the main protective conductor
CAN bus
DO 8
Controller
Reinforced
insulation
U+
U-
1-pole with
1-pole with connected
connected
positive
negative
R z
2-pole
R z
R z