Characteristics/details
No function
–
Power supply LED does not light
up
No function
–
AVR STATUS LED does not light
up
Relay chatter
Table 6: General faults
Characteristics/details
Display
–
No display.
Connection cannot be established
with visualization
Incorrect display of visualization in
the web browser.
Table 7: Human-machine interface
7 Fault elimination
7.1 General faults
Cause
No power supply.
Fuse tripped.
Configuration error
High EMC load.
Poor grounding.
7.2 Human-machine interface
Cause
Power supply interrupted.
Fuse faulty.
Connection cable defective.
SSL encryption active.
PC not in same subnet as visualiza-
tion.
Access to the visualization using a
web browser after a software up-
date.
7.3 Other faults
If you cannot resolve a problem, please contact Maschinenfabrik Reinhausen.
Please have the following data ready:
–
Serial number
–
Nameplate
–
Software version
Remedy
Check the power supply.
Contact Maschinenfabrik Reinhausen GmbH.
Contact Maschinenfabrik Reinhausen GmbH.
Use shielded cables or external filters.
Check the functional ground.
Remedy
Check the power supply.
Contact Maschinenfabrik Reinhausen.
Check connection cable.
Accept SSL certificate in browser.
Call up IP address using https://.
Deactivate SSL encryption.
Check the setting of IP addresses of the device and
PC and correct if necessary.
Delete the web browser's cache.
7820658/06 EN Fault elimination