Descargar Imprimir esta página

Xylem SP Serie Manual De Instrucciones página 3

Publicidad

Idiomas disponibles

Idiomas disponibles

SAFETY INSTRUCTIONS
TO AVOID SERIOUS OR FATAL PERSONAL INJURY OR
MAJOR PROPERTY DAMAGE, READ AND FOLLOW ALL
SAFETY INSTRUCTIONS IN MANUAL AND ON PUMP .
This is a SAFETY ALERT SYMBOL. When
you see this symbol on the pump or in
the manual, look for one of the following
signal words and be alert to the potential
for personal injury or property damage.
Warns of hazards that WILL cause serious
DANGER
personal injury, death or major property
damage.
Warns of hazards that CAN cause serious
WARNING
personal injury, death or major property
damage.
Warns of hazards that CAN cause per-
CAUTION
sonal injury or property damage.
NOTICE: INDICATES SPECIAL INSTRUCTIONS
WHICH ARE VERY IMPORTANT AND
MUST BE FOLLOWED.
THIS MANUAL IS INTENDED TO ASSIST IN THE
INSTALLATION AND OPERATION OF THIS UNIT
AND MUST BE KEPT WITH THE PUMP.
MAINTAIN ALL SAFETY DECALS.
UNIT NOT DESIGNED FOR USE
WARNING
WITH HAZARDOUS LIQUIDS OR
FLAMMABLE GASES.
Hazardous fluids can
cause fire, burns
or death.
NOTICE: INSPECT UNIT FOR DAMAGE AND
REPORT ALL DAMAGE TO THE CARRIER
OR DEALER IMMEDIATELY. DO NOT USE
PUMP IF DAMAGE IS SUSPECTED.
This product can expose you to
WARNING
chemicals including Lead, which is
known to the State of California to cause cancer or
birth defects or other reproductive harm. For more
information go to: www.P65Warnings.ca.gov.
DESCRIPTION AND SPECIFICATIONS
• The SPM/SPH Series embraces a line of end suction
single stage, self-priming centrifugal pumps for lawn
sprinkling, HVAC systems, and general water transfer.
• Casing is cast iron construction with tapped openings
provided for vacuum gauge and casing drain.
• Impeller is bronze, enclosed design, balanced for smooth
operation and keyed to motor shaft.
• ALL motors are NEMA standard, 3500 RPM, open drip
proof or TEFC enclosure.
ENGINEERING DATA
• Maximum Liquid Temperature: 160º F (71º C)
• Starts per hour: 20 – evenly distributed.
PIPING
• Pump MUST be installed horizontally on a solid flat
surface, with discharge on top.
• Allow adequate space for servicing and ventilation.
Protect the unit from weather and water damage due to
rain or flooding or freezing temperatures.
• Piping should be no smaller than the suction and dis-
charge connections and kept as short as possible, avoid-
ing unnecessary fittings to minimize friction losses.
• All piping MUST be independently supported and MUST
NOT place any piping loads on the pump.
NOTICE: DO NOT FORCE PIPING INTO PLACE AT
PUMP SUCTION AND DISCHARGE
CONNECTIONS.
• The use of Teflon™ tape, or equivalent, is recommended
for ALL pipe joints.
• All pipe joints MUST be airtight.
PIPING – SUCTION
• Total suction lift, including elevation and pipe friction loss,
should not exceed 25 feet.
• Install an airtight union in the suction line close to the
pump. See Figure 1.
FUSED OR
CIRCUIT BREAKER
DISCONNECT MEANS
Figure 1
• Installation of a foot valve at the liquid source, or a check
valve after the pump discharge, is recommended.
NOTICE: FOR INSTALLATIONS WITH LONG SUCTION
PIPING, BOTH A FOOT VALVE AND A
CHECK VALVE ARE RECOMMENDED.
• To avoid air pockets, no part of the piping should be
above the pump suction connection and piping should
slope upward from liquid source.
• For installations with long suction piping, fill the suction
pipe with water before connecting to pump.
• To ensure proper level installation of the pump utilize
included shims (13K248-0.75" or 13K346-1.75") under
motor feet.
PRIMING
OPENING
DISCHARGE
UNION
SUCTION
3

Publicidad

loading

Este manual también es adecuado para:

Sp im181r05