10.5 Wall mounting
D
A
B
C
3
Fig. 18: Wall mounting
Key
1
Screws for mounting (4x)
2
Fastening anchors [S12-Ø12 mm / 25 mm ]
A
Minimum clearance: 486 mm
Recommended clearance: 735 mm
B
Minimum clearance: 300 mm
C
Minimum clearance: 500 mm
D
Recommended clearance: 1000 mm
10.6 Requirement for supply lines and fuse
DC-side
Max. conductor cross-section
Min. cable cross-section
Length of insulation to be stripped off
Recommended cable type
Connection type
Combiner box
AC-side
Max. conductor cross-section
Min. cable cross-section
4
Option: 50 mm² with 2x5 AC cable (for daisy chain). The optionally available input plate is required for this! Ac-
cessories [See section 4.4} Page 14]
M8 / M10
8 mm
676 mm
1
2
A
max. 20 mm
12 mm
Fig. 19: Minimum clearances for wall mounting
3
4
1)
1)
-
-
-
908 mm
1543 mm
486 mm
Bolt with lock nut (2x)
U-lock (not in scope of supply)
Minimum clearance excluding device:500 mm
Recommended clearance excluding device:766,5
mm
-
-
6mm²
2.5mm²
15 mm (see insert in scope of delivery)
in accordance with local installation standards
Phoenix adapter/ PV-C3F-S 2.5-6 (+) 1100 V/35 A
Phoenix adapter/ PV-C3M-S 2.5-6 (-) 1100 V/35 A
yes
240mm² (AL or CU)
4
50mm² (AL or CU)
510 mm
486 mm