NOTE
If the device is connected, the overvoltage conductors / varistors contained in the device have an impact on
the electrical system insulation resistance test as per HD 60364-6 / IEC 60364-6 Low-voltage installations-
Part 6: Verification.
IEC 60364-6 6.4.3.3 describes two options for this case. The first option is to disconnect devices with an
overvoltage conductor or, if this is not practicable, then the test voltage can be reduced to 250V.
3
Installation
3.1
Choosing the installation location
DANGER
Risk of fatal injury due to fire or explosions
Fire caused by flammable or explosive materials in the vicinity of the device can lead to serious injuries.
Do not mount the device in potentially explosive atmospheres or in the vicinity of highly flammable ma-
terials.
CAUTION
Risk of property damage due to gases that have an abrasive effect on surfaces when they come into con-
tact with ambient humidity caused by weather conditions!
The device housing can be seriously damaged due to gases in combination with air humidity resulting from
weather conditions (e.g. ammonia, sulphur).
If the device is exposed to gases, it must be installed in a location that is visible.
Perform regular visual inspections.
Immediately remove any moisture from the housing.
Ensure adequate ventilation at the installation location.
Immediately remove dirt, especially on vents.
Failure to observe these warnings may result in damage to the device that is not covered by the war-
ranty.
NOTE
Access by maintenance personnel for service
Any additional costs arising from unfavourable structural or installation conditions will be billed to the cus-
tomer.
Installation space
ž
As dry as possible, climate-controlled, the waste heat must be dissipated away from the device.
ž
Unobstructed air circulation.
ž
Close to the ground, accessible from the front and sides without requiring additional resources.
ž
In outdoor areas, KACO new energy recommends protecting the device from direct weather exposure and sun-
light. This should be carried out by means of constructional measures (e.g. wind breaks) in order to reduce thermal
heating of the components, premature derating and more extensive wear of the fans.
Installation surface
ž
Must have adequate load-bearing capacity
ž
Must be accessible for installation and maintenance
ž
Must be made out of heat-resistant material (up to 90 °C )
ž
Must be flame resistant
ž
Minimum clearance during installation: See comprehensive manual under
loads
3.2
Tools used
Sym-
Shape of
bol
the connector
External hexagon
W
Torx
T
Tab. 1: Key and description of tool codes
3.3
Preparing the installation location
KACO blueplanet 100 NX3 KACO blueplanet 125 NX3
Sym-
Shape of
bol
the connector
Internal hexagon
A
Slot
S
www.kaco-newenergy.com/de/down-
Tightening torque
Spanner size or number
Outer contour
Fig. 1: Presentation format
Nm