Descargar Imprimir esta página

EBARA Ego 2 slim Serie Manual De Instalación Y Operación página 33

Ocultar thumbs Ver también para Ego 2 slim Serie:

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 70
3.4.2.5.1 MODBUS
Slave address
Maximum Modbus
packet size
Supported baud rates
Stop bits
Parity bit
3.4.2.5.2 BACNET
Device MAC address
Maximum ADPU size
Supported baud rates
Mode 3 and 4 is used for PWM control and feedback according to IEC 60469-1. The difference between these
two modes is in response to PWM-in signal. Mode 3 stops the pump when signal is missing or at 0 % while Mode
4 applies full power.
Terminal
designation
SET1 / RUN
PWM-in (PWM input)
Signal frequency: 100 Hz – 10000 Hz (1000 Hz nominal)
Signal load: 5 mA (4 – 6 mA, internally limited)
Signal amplitude: 3.3 – 24 V (threshold at approx. 3V)
COM / 0V
Common ground for signals
SET2 / MAX
PWM-out (PWM output)
Signal frequency: 75 Hz (±1 Hz)
Signal drive: Open drain, (100 ohm, 20 mA internal current limit)
Signal amplitude: 0 – 24 V
Signal polarity: Active high (0% - pulled to COM, 100% -open)
SET3 / FB
FB (10.5 V) output, can be used to supply SET1 and SET2 bias.
Modbus RTU over RS-485
1-247
256 bytes
1200, 2400, 4800,
9600, 19200, 38400
1 or 2
Even/odd/none
BACnet MS/TP over RS-485
1-127
92 bytes
9600, 19200, 38400
See section 6.5 Speed, parity and address.
[default=245]
Including address (1) and CRC (2) bytes.
Settable over Modbus register.
Settable over Web interface (tab "Network").
[default=19200]
1 stop bit minimum, up to 2 when parity not
enabled
[default=1]
[default=Even]
Settable over Web interface (tab "Network")
[default=1]
Settable over Web interface (tab "Network")
[default=38400]
Signal function
32
32

Publicidad

loading