4 Commissioning
4.1 Preliminary checks
Before commissioning the dryer, make sure:
• installation was carried out according that given in the section 3;
• the air inlet valves are closed and that there is no air fl ow through the dryer;
• the power supply is correct;
4.2 Starting
1. Start the dryer before the air compressor by
means of the main power switch "QS", the display
shows "DRY"
;
2. after at least 5 minutes slowly open the air
inlet valve and subsequently open the air outlet
valve: the dryer is now performing its air drying
function.
4.3 Operation
• Leave the dryer on during the entire period the air compressor is working;
• the dryer operates in automatic mode, therefore fi eld settings are not required;
• in the event of unforeseen excess air fl ows, by-pass to avoid overloading the dryer.
4.4 Stop
1. Stop the dryer 2 minutes after the air compressor stops or in any case after interruption of the air
fl ow;
2. do not allow compressed air to fl ow through the dryer when the latter is not running;
3. switch off at the main power switch «QS». The power light goes out and the compressor stops.
English
5 Control
5.1 Control panel
QS
UP button: press to increase the value of a selected editable parameter.
DOWN button: press to reduce the value of a selected parameter.
esc
ESC button :returns to the previous level
set
SET button : one single press to see the alarms, press for more seconds to enter Menu
5.2 Symbol
Symbol
q
SPS004- SPS100
PRESSED FOR 3s START MANUAL CONDENSATE DRAIN
(Service e Factory)
Symbol
Function
status
Lit up
Dew point correct
Flashing
Warning dew point high/low
Off
Alarm dew point
Lit up
Condensate drain ON
Off
Condensate drain OFF
Flashing
Warning "maintenance"
Symbol
Symbol
Function
status
illuminated
grade
illuminated
Alarm
4/8

Publicidad

loading