Troubleshooting /
ENG
Fault: Pump runs all the time
1. Is float positioned with magnet facing upwards?
2. a) Is the float located inside the reservoir around
the sensor column?
b) Is the top clipped firmly on to the reservoir?
3. Is there sludge inside the reservoir preventing
the float from resting on the reservoir bottom?
This may occur if pump has been operated for
some time without cleaning. Clean with an anti
bacterial cleansing solution. NOTE; The pump will
only switch off when the float is actually resting
on the bottom of reservoir.
4. Does evaporator produce more condensate than
pump can handle. If so, pump is too small and
must be replaced with a different type.
Fault: Vibration noise
1. Is pump in contact with any hard surface causing
vibration or with Sheetrock which will amplify
vibration?
2. Has appropriate sound deadening and anti
vibration padding been placed between pump
and contact surfaces?
Fault: Sweating in High Humidity conditions
1. Is the first 6' of discharge hose insulated?
ES
Falla: La bomba funciona permanentemente
1. ¿Está el flotador dispuesto con el imán hacia
arriba?
2. a) ¿Está el flotador dentro del depósito alrededor
de la columna del sensor?
b) ¿Está la tapa del depósito asentada firmemente
en el depósito?
3. ¿Hay lodo o suciedad que impida que el
flotador baje? Esto puede ocurrir si no se da
mantenimiento a la bomba periodicamente. Es
necesario limpiar con una solucion antibacterial.
NOTA; La bomba sólo apagará cuando el flotador
esté realmente posado en el fondo del depósito.
4. ¿Produce el evaporador más agua de
condensación de la que pueda procesar la bomba?
De ser asÌ, la bomba es demasiado pequeña y se
debe reemplazar por una distinta.
Falla: Ruido de vibraciones
1. ¿Está la bomba en contacto con cualquier
superficie dura que causa vibraciones o con yeso
que pude amplificar las vibraciones?
2. ¿Se ha instalado material de relleno insonorizante
y antivibración adecuado entre la bomba y las
superficies de contacto?
Falla: Condensación en condiciones húmeda
1. ¿Está aislado el primer tramo de 6' de la manguera
de descarga?
12
Localización de Averías
Fault: Pump runs but does not discharge any
water
1. a) Is drain outlet hose from evaporator connected
onto drain inlet nipple on reservoir?
b) Is reservoir outlet connected to pump inlet?
c) Are there any restrictions in drain hose?
d) Is discharge hose connected to pump outlet
barb?
e) Are there any restrictions in discharge hose or
breather tube?
f) Check that reservoir, filter and discharge hose
are free of sludge and debris.
g) If pump discharge hose is connected into a
manifold, ensure there is no back pressure in
manifold to prevent pump from discharging.
Fault: Pump doesn't operate at all
1. a) Is power reaching the pump?
b) Check fuse for continuity.
c) Is it correctly wired?
d) Does the pump voltage match the evaporator
voltage?
e) Is there sufficient voltage at evaporator
terminals to drive pump?
2. Is pump very hot? A thermal cut out may have
been activated to protect pump. This will
automatically reset once the pump has cooled
down.
Falla: La bomba funciona pero no descarga
agua
1. a) ¿Se encuentra la manguera de desagüe del
evaporador conectada a la entrada de desagüe
en el depósito?
b) ¿Esta la manguera de desagüe de el depósito
conectada a la entrada de la bomba?
c) ¿Hay obstrucciones en la manguera de desagüe?
d) ¿Está la manguera de descarga conectada a la
punta de la salida de la bomba?
e) ¿Hay obstrucciones en la manguera de descarga
o en el tubo respirador?
f) Comprobar que el depósito, filtro y manguera
de descarga estén libres de lodo o suciedad?
g) Si la manguera de descarga de la bomba está
conectada a un colector, asegúrese de que no
haya ninguna contrapresión en el colector que
impida la descarga de la bomba?
Falla: La bomba no funciona en absoluto
1. a) ¿Recibe alimentación la bomba?
b) Comprobar la continuidad del fusible.
c) ¿Está cableada correctamente?
d) ¿Coincide el voltaje de la bomba con el del
evaporador?
e) ¿Hay suficiente voltaje en los terminales del
evaporador para accionar la bomba.
2. ¿Esta muy caliente la bomba? Puede que se haya
activado una corte termico para protegerla. Una
vez que se haya enfriado, la bomba se restablecera
automaticamente.