5. Electrical work
5.7. Switch setting for high ceiling (Fig. 5-9)
With this unit, the air fl ow rate and fan speed can be adjusted by setting the SW21-1 and SW21-2. Select a suitable setting from the table below according to the installa-
tion location.
* Make sure the SW21-1 and SW21-2 switch are set, otherwise problems such as not getting cool/warm may occur.
SW21-1
SW21-2
Silent
ON
Standard
OFF
OFF
High ceiling
ON
OFF
5.8. Switch setting for i-See sensor (Fig. 5-9)
With i-See sensor panel, SW3-4 must be adjusted as a position of i-See sensor. (Refer to page 16.)
SW3-4
Position 1
OFF
Position 3
ON
5.9. Switch setting for horizontal airfl ow direction (Fig. 5-9)
The angle of the horizontal airfl ow direction can be changed using SW3-5.
SW3-5
Draft-less
OFF
Downward setting
ON
5.10. Electrical characteristics
Model
PLFY-WL04NFMU-E
PLFY-WL06NFMU-E
PLFY-WL08NFMU-E
PLFY-WL12NFMU-E
PLFY-WL15NFMU-E
5.11. How to set the fi xed up/down air direction (Only for wired remote controller)
• For PLFY-NFMU, only the particular outlet can be fi xed to certain direction with
the procedures below. Once fixed, only the set outlet is fixed every time air
conditioner is turned on. (Other outlets follow UP/DOWN air direction setting of
the remote controller.)
■ Explanation of word
• "Address No. of indoor unit" is the number given to each air conditioner.
• "Outlet No." is the number given to each outlet of air conditioner.
(Refer to the right.)
• "Up/Down air direction" is the direction (angle) to fi x.
Horizontal airfl ow
Remote controller setting
The airfl ow direction of this outlet is controlled by
the airfl ow direction setting of remote controller.
Height
2.5 m, 8.2 ft
2.7 m, 8.9 ft : default setting
3.0 m, 9.8 ft
"□" stamp position
"○" stamp position : default setting
Default setting
Power supply
Volts/ Hz
Range +- 10%
Max.: 253V
208/230V / 60Hz
Min.: 198V
Downward
Fixed setting
The airfl ow direction of this outlet is fi xed in
particular direction.
* When it is cold because of direct airfl ow,
the airfl ow direction can be fi xed horizon-
tally to avoid direct airfl ow.
Symbols: MCA: Max. Circuit Amps (= 1.25×FLA)
IFM: Indoor Fan Motor
MCA (A)
0.36
0.36
0.36
0.36
0.36
Electric component box
Outlet No. 4
Outlet No. 3
Note:
The outlet No. is indicated by the number of grooves on both ends of each
air outlet. Set the air direction while checking the information shown on the
remote controller display.
Air outlet identifi cation marks
FLA: Full Load Amps
Output: Fan motor rated output
IFM
Output (kW)
FLA (A)
0.05
0.29
0.05
0.29
0.05
0.29
0.05
0.29
0.05
0.29
Outlet No. 1
Outlet No. 2
en
11