- Press
: the value of parameter 13 flashing press
to select the gas, refer to the table below:
PARAMETER 02
NATURAL GAS (G20)
BUTAN (G30)
PROPAN (G31)
- Confirm by pressing
At the end of the procedure, the appliance displays alarm AL62
which indicates that the gas valve requires calibration.
Exit from the menu automatically stops after 5 minutes of
inactivity or by pressing and holding the
til the display shows MENU' flashing, release the button:
the display shows the set temperature value.
Calibration gas valve
Before calibration check the mains pressure: 20 mbar for
Natural gas - 37 mbar for LPG.
After each replacement of the electronic board or gas valve,
set the appliance (complete electronic calibration
The calibration of gas valve cancels the values (min/max)
set at the factory.
The view, by means of a pressure gauge connected to
the gas valve, of the pressure values (min/max) set at the
factory, is carried out through the Manual Calibration (see
chapter Service Menu).
- Place the electric switch of the system to off and remove the
casing
- Remove the cover that closes the service inlet (located on the
shelf - fig. 11 pag. 61) and insert through the hole the silicon
pressure gauge tube
- Loosen by approximately two turns the screw of the pressu-
re tap downstream (P-OUT) of the gas valve and connect the
pressure gauge to it (fig. 11 pag. 61)
- Carefully close the casing and place the electric switch of the
system to on
keys until the display shows Ma followed
- Press the
and
by nu to form the word Manu (fig. 20 pag. 61)
- Press the key
until the display shows Au followed by to form
the word Auto (fig. 20 pag. 61)
- Open the hot water tap at maximum
- The display shows P01 indicating that the appliance is opera-
ting at maximum capacity
- Scroll with
and
keys until the maximum pressure value of
the burner is shown on the pressure gauge (ref. technical data)
- To store the value press the button
- Press the button
to select the next lowest setting value P00
- Scroll with
and
keys until the minimum pressure value of
the burner is shown on the pressure gauge (ref. technical data)
- Press
to save the value
until Manu flashes. Release the key and the set
- Press
temperature value is shown on the display
- Close the hot water tap
The calibration operation ends automatically after 15
minutes of inactivity or in the case of overtemperature
(67°C).
In case of power loss it is necessary to repeat the procedure.
and
PARAMETRO 13
0
0
1
2
1
1
button un-
).
USE OF THE APPLIANCE
CONTROL PANEL fig. 29 pag. 63
Preliminary checks
Check that:
- The data of the power supply networks corresponds to that stat-
ed on the data plate
- The data plate information corresponds to that of the power
supply networks (electric, water, gas)
- The installation complies with the local regulations in force
- The electrical connection to the mains and of the earthing con-
nection have been performed correctly.
Appliance start-up
Following the necessary checks, proceed with the following op-
erations:
Electrically power the water heater
Open the gas valve installed upstream of the water heater
Open the water tap at the bottom of the water heater
- Press the power button
- The display shows:
1. Software review
2. The type of gas for which the water heater was designed:
(G20) -
(G30) -
3.
Low Emission product
4. Model
5. Symbols test (display ON)
With the first ignition procedure completed, the display shows
the symbols
(fig. 16 pag. 61).
Press the button
to power the water heater, the display shows
the set point temperature, the symbol
quest in progress) and the symbol
17 pag. 61).
Water temperature adjustment
The water temperature can be set between 37 and 60°C.
- Use
and
to increase and decrease the water temperature,
the symbol
flashing for 5 seconds and the display shows
the new temperature.
Contact with hot water at a temperatu-
re ≥50 ° C can cause severe burns.
For daily use of the appliance it is re-
commended to set the temperature at
a value not exceeding 50°C.
The appliance is set to maintain a constant water tempe-
rature. It could happen that in the case of withdrawals at
extremely low flow rates, the water temperature rises abo-
ve the set value, causing burns. It is advisable to check
always the water temperature before any use.
Set point regulation
To reduce gas consumption and prevent limescale in the heat
exchanger, it is recommended to set the appliance at the mini-
mum temperature most suitable for the domestic use.
Recommended temperature setting:
Kitchen
50°C - 55°C
A cause of the system and environmental conditions could be a
discrepancy between the temperature set on the appliance and
that actually supplied to the user.
21
(G31)
(in case hot water re-
(in case of burner ON) (fig.
≥50°C
Bathroom
37°C - 45°C

Publicidad