Firmware update via memory card
then to the Downloads area. Then click See all. Here you will find the .zip file that contains the files needed to
load the firmware. Download and save the file to a known location on the hard disk.
3.
Repeat steps 2 to 10 of section of the display update section.
4.
Check that the firmware version installed on the inverter has changed to the new version.
Troubleshooting in the firmware loading process
In the event that it was not possible to load the firmware, check the following:
Possible problem
Impaired memory card or the model used is incompatible with
the inverter.
ERROR 2: The SD card is not valid or has not been recognized.
ERROR 8: Loading the firmware has not completed for a certain
reason. It might not need to be updated because the version you
are trying to load is the same one as already installed.
Error different to those previously described.
If it is not possible to load via the SD card, connect the inverter to a computer, run the INGECON SUN Manager
software and load the firmware through said software. You can find the instructions to load the firmware at the
INGECON SUN Training website in the courses section (http://www.ingeconsuntraining.info/?page_id=4127).
If it is not possible to complete the update after the previous points, contact the Ingeteam Technical Service.
ABI2012IQM02_A - User manual
Solution
As far as possible, try another better-quality card.
Try to reformat it. If this does not work try another card.
Check that the downloaded version is newer than the one
installed in the inverter, taking steps 1 and 2.
Contact the Ingeteam Technical Service.