Descargar Imprimir esta página

Grohe 43 863 Manual De Montaje página 9

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 13
III. Electronics module
1. Disconnect plug-in connectors from electronic module (A) to
solenoid valve (E), to sensor (B) and to transformer (F), see
Fig. [15].
2. Detach electronic module (A) from bracket.
Assemble in reverse order.
After reconnecting power supply, position detection begins.
IV. Sensor
1. Disconnect plug-in connector between sensor cable (B1)
and electronic module (A), see Fig. [16].
2. Close isolating valve (H), see Fig. [2].
Fault/ cause/ remedy
Fault
No flushing
Water flowing continuously
Undesired flushing
Flow volume too low
Flow volume too high
Position detection is not
performed (No flushing)
3. Remove urinal.
4. Turn retaining tabs (C) and remove sensor (B), see Fig. [5].
Assemble in reverse order.
Disconnect and reconnect plug-in connector between
electronic module (A) and transformer (F), see Fig. [12].
After reconnecting power supply, position detection begins.
Replacement parts, see fold-out page I
( * = special accessories).
Cause
• Water supply interrupted
• Filter in solenoid valve blocked
• Plug-in connector without contact
• The detection zone of the sensor system
is set too low/too high
• Solenoid valve defective
• Transformer faulty
• Software lock activated because
compensation routine has been
performed 25- times
• Electronics defective (indicator lamp
not flashing or permanently on)
• Solenoid valve defective
• The detection zone of the sensor system
is set too high
• Flow volume set too low
• Filter in solenoid valve defective
• Filter in solenoid valve blocked
• Solenoid valve defective
• Flow volume set too high
• Solenoid valve defective
• Replacement part exchanged,
no position detection
• Software lock activated because
compensation routine has been
performed 25- times
Remedy
- Open isolating valve
- Clean or replace filter, see Solenoid
valve and filter maintenance
- Attach plug-in connector
- Increase/reduce range, see Settings,
Setting the range
- Replace solenoid valve, see Solenoid
valve and filter maintenance
- Replace transformer, see Transformer
maintenance
- Reset counter, see Resetting counter
- Replace electronic module, see
Maintenance of electronic module
- Replace solenoid valve, see Solenoid
valve and filter maintenance
- An opposite object will be detected.
Reduce range, see Settings,
Setting the range
- Adjust flow volume, see Settings,
Setting the flow volume
- Clean or replace filter, see Solenoid
valve and filter maintenance
- Clean or replace filter, see Solenoid
valve and filter maintenance
- Replace solenoid valve, see Solenoid
valve and filter maintenance
- Adjust flow volume, see Settings, Setting
the flow volume
- Replace solenoid valve, see Solenoid
valve and filter maintenance
- Reset counter, see Resetting counter
- Reset counter, see Resetting counter
6

Publicidad

loading