11 - PHOTOCELLS
The unit has two inputs for photocells (normally closed contact),
which can be independently enabled and associated with different
functions:
1. Photocell active during opening and closing phases
• During the movement of the gate, in any direction, if the
photocell is interrupted the gate stops; when the interruption is
removed the gate opens completely.
• With the gate closed, if the photocell is interrupted the
start-up commands are rejected.
• With the gate open, if the photocell is interrupted the pause
time is reset, and the closing commands are rejected.
Connect the N.C. output of the photocell between terminals S5
and S9 (configure the
FOT1
2. Photocell activated when closing and gate stopped
• During opening if the photocell is interrupted has no effect
• During closing, if the photocell is interrupted the gate
completely re-opens
• With the gate closed, if the photocell is interrupted the
start-up commands are rejected.
• With the gate open, if the photocell is interrupted, the pause
time is reset and the closing commands are rejected.
Connect the N.C. output of the photocell between terminals S6
and S9 (configure the parameter
3. Photocell activated only during closing
• During opening and with the gate closed, if the photocell is
interrupted has no effect
• During closing, if the photocell is interrupted the gate
completely re-opens
• With the gate open, if the photocell is interrupted, the pause
time is reset and the closing commands are rejected.
Connect the N.C. output of the photocell between terminals
S6 and S9 (configure the parameter
m
WARNING:
• If you connect multiple photocells on the same terminal, the
connection must be done in series: all photocells will have the
same function.
• If you do not connect any photocell to terminal S5, the menu
must be set to
FOT1
NO
• If you do not connect any photocell to terminal S6, the menu
must be set to
FOT2
NO
Regardless of the selected function, if the photocells are activated
during the pause, the pause time is reset using the value set in
parameter
.
CH.AU
If you want to accelerate the closing of the gate, after the transit,
set a value for the parameter
The pause time can be reset using the value of
If you want to stop the gate after transit through the photocells,
set the value
for the parameter
YES
NOTE: if the photocells are connected on the two FOT1 and
FOT2 inputs the gate stops only after the passage in front of both
photocells have been detected
- 46 - ENGLISH
parameter on
)
APCH
on
)
FOT2
CFCH
on
)
FOT2
CFCH
.
.
lower than
CH.TR
CH.AU
.
CH.TR
PA.TR
11.1 - POWER OF PHOTOCELLS AND AND
FUNCTIONAL TEST
Photocells can be powered to 24 Vac (FIG.1) or 12 Vdc (FIG.2).
Regardless of the selected function, the photocells can be tested
prior to each movement.
To enable the photocell test it is required to indicate the maximum
duration of the test in the parameter FO.TE: if set to NO, the test
is not carried out.
POWER SUPPLY 24VAC
Connect the power supply of photocell receivers between
terminals E1 and E3 (COM).
Connect the power supply of photocell transmitters between
terminals E5 and E3 (COM).
NOTE: to facilitate wiring the terminals for the AC power supply
are double (E1 = E2 / E3 = E4)
WARNING: To carry out the test it is necessary that the
transmitter power of the photocells is connected to the terminals
E5 and E3 (COM)
POWER SUPPLY 12VDC
The DC power supply is available between terminals
H8 (+) and H7 (-).
ATTENTION: In order to perform the test, one of the relay options
must be used:
• REL1: connect the transmitter power supply between terminals
Z3 (+) and H7 (-) and connect the terminal H8 with the
terminal Z4, set the
• REL2: connect the transmitter power supply between terminals
Z5 (+) and H7 (-) and connect the terminal H8 with the
terminal Z6, set the
's.
parameter to
.
REL1
TEST
parameter to
REL2
TEST
.