Problems
"XXXX" display
The setup isn't working (load not showing, unstable)
"Overload" displayed
"-___-" displayed
The product does not control the relays
For any other issues related to the accessories and sensors, see the manuals.
Copy of the declaration of conformity in the appendix.
12. Troubleshooting
Possible causes
Link lost with a networked sensor
Bad connection
Defective electronics
Electromagnetic environmental
disturbances
Sensor overload
Incorrect gain setting
Sensor compressed
The thresholds have not been
stored
13. Declaration of conformity
Remedies
Turn off the "master"
DMU monitor and restart
the network
Check all parts are
connected properly
Contact Tractel
®
Check the correct wiring
of the RS485 cable
shielding and earth
connection compliant
with the devices
Force exceeds the
sensor's limits
Poor adjustment of the
installation
Remove any
compression forces
Start the threshold
setting again. The light
indicators must be
turned on to indicate the
setting is correct