Recommended Contactors; Soft-Starter Ssw-07 Connection To The Motor - WEG SSW-07 Manual Del Usuario

Arrancador suave
Ocultar thumbs Ver también para SSW-07:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

CALL NOW 800-985-6929
Chapter 3 - INStaLLatION aND CONNeCtION
3.2.4.3 Recommended
Contactors
3.2.5 Soft-Starter
SSW-07
Connection to
the Motor
20
CALL NOW 800-985-6929
http://www.automatedpt.com/
When the SSW-07 is used in applications that require an isolator
contactor, according to the figure 3.10 (K1), the use of WEG
contactors is recommended.
SSW-07 Model
table 3.8 - Recommended contactors
DANGER!
Power factor correction capacitors must never be installed at the
output of the Soft-Starter SSW-07. (U / 2T1, V / 4T2 and W / 6T3).
ATTENTION!
To ensure that the protections based on the current reading and
display operate correctly, for example the overload, the motor
nominal current must not be lower than 50 % of the nominal Soft-
Starter SSW-07 current.
NOTE!
Use the wire sizes and fuses recommended in tables 3.5, 3.6 and
3.7. The connector tightening torque is indicated in table 3.4. Use
only copper wires.
NOTE!
The Soft-Starter SSW-07 is provided with electronic protection
against motor overload. This protection must be set according to
the specific motor. When several motors are connected to the same
Soft-Starter SSW-07 use individual overload relays for each motor.
http://www.automatedpt.com/
WEG Contactor
17 A
CWM18
24 A
CWM25
30 A
CWM32
45 A
CWM50
61 A
CWM65
85 A
CWM95
130 A
CWM150
171 A
CWM180
200 A
CWM250
255 A
CWM250
312 A
CWM300
365 A
CWME400
412 A
CWME400
Email: charles@automatedpt.com
Email: charles@automatedpt.com

Publicidad

Tabla de contenido
loading

Tabla de contenido