Capacity Of The Power Supply Line; Table Of Fuses And Contactors; Dimensions - WEG SSW-05 Manual Del Usuario

Ocultar thumbs Ver también para SSW-05:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

8. CAPACITY OF THE POWER SUPPLY LINE:

The SSW-05 Plus is suitable to be used in circuits that can not supply more than X A
to table below) symmetric Ampères, Y Volts maximum:
SSW-05 Plus
Y = 220- 575V
Model
X (kA)
3A
10A
16A
23A
30A
45A
60A
85A
10
9. TABLE OF FUSES AND CONTACTORS (SEE ITEM 11):
SSW-05 Plus
Contactor
Model
(K1)
3A
CWM09
10A
CWM12
16A
CWM18
23A
CWM25
30A
CWM32
45A
CWM50
60A
CWM65
85A
CWM95

10. DIMENSIONS:

Width
Size
mm (in)
mm (in)
L
La
H
1
59
60.4
130
(2.32) (2.38)
(5.12) (5.15)
2
79
80.4
185
(3.11) (3.17)
(7.28) (7.31)
Notes
1) The SSW-05 Plus can be fixed on DIN 35mm rail.
2) If the fastening is made through a M4 bolt, bolt tightening torque should not be higher
than 1 Nm (8.85 Ib in). The use of a top fastening support is required as shown in figure
bellow:
Figure 10.1 - SSW-05 Plus Dimensions
5
5
5
5
5
5
5
Fuse
(F1, F2,F3)
Type D 10A
Type D 16A
Type D 25A
Type D 35A
Type D 50A
Type D 63A
Type NH 100A
Type NH 125A
Depth P
Fixing A
Height
mm (in)
Ha
130.7
145 (5.70)
51 (2.00)
172 (6.77)
71 (2.79)
185.7
English-7
Installation and Operation Manual - SSW-05 Plus
Fuse
(F11, F12, F21)
Type D 6A
Fixing B
Fixing D
mm (in)
mm (in)
mm (in)
122 (4.80)
61 (2.40)
177 (6.17)
99 (3.89)
(according
RMS
Weight
Fixing
kg (Lb)
M4 screw/ Rail
0.74 (1.63)
M4 screw/ Rail
1.67 (3.68)

Hide quick links:

Publicidad

Tabla de contenido
loading