3.3 RECOMMENDED
SET-UPS
CALL NOW 800-985-6929
http://www.automatedpt.com/
Chapter 3 - INStaLLatION aND CONNeCtION
Some recommended set-ups are shown here and they can be
completely or partly used.
The main warning notes for all the recommended set-ups are
shown below and are described in the schemes by their respective
numbers.
NOTES!
The use of fuses or circuit breakers at the input circuit is
1
necessary for the entire installation protection. It is not necessary
to use ultra-fast fuses for the SSW-07 operation; however, their
use is recommended for the soft-starter complete protection.
The transformer "T1" is optional and must be used when there
2
is a difference between the line voltage and the electronic power
voltage.
In case that damage at the SSW-07 Soft-Starter power circuit
3
keeps the motor running (e.g., shorted thyristors), the motor
protection is obtained with the use of the power isolating
contactor (K1) or circuit breaker (Q1).
Start push-button.
4
Stop push-button.
5
Start/Stop switch. Bear in mind that when using two-wire digital
6
input command (normally open switch with retention), in case
of a power interruption, upon return of power, the motor will be
started immediately if the switch remains closed.
In case of maintenance of the Soft-Starter SSW-07 or the motor
7
it is necessary to remove the input fuses or disconnect the power
supply to ensure the complete equipment disconnection from
the power supply.
8
The emergency stop can be used by disconnecting the
electronics power supply.
9
Undervoltage release for the Q1 power isolation circuit breaker.
http://www.automatedpt.com/
Email: charles@automatedpt.com
23