First Time Power-Up and Start-Up
Step
Action/Display Indication
11
If necessary, change "P0398 – Motor
Service Factor" parameter. This change
will affect the current and the time of the
motor overload protection operation.
Press the
key to the next parameter.
13
If necessary, change "P0401 – Motor
Rated Current" parameter. This change
will affect P0156, P0157, P0158 and P0410.
Press the
key to the next parameter.
15
If necessary, change "P0403 – Motor
Rated Frequency " parameter. This
change will affect P0402.
Press the
key to the next parameter.
17
If necessary, change "P0405 – Encoder
Pulse Number" according to the encoder
model.
Press the
key to the next parameter.
19
If necessary, change "P0408 – Run Self-
Tuning" parameter.
Press the
key to the next parameter.
Run the self-tuning when running in V V W
and vector modes.
50 | CFW700
Step
12
If necessary, change "P0400 – Motor
Rated Voltage" parameter. This change
corrects the output voltage by the factor
"x = P0400/P0296".
Press the
14
If necessary, change "P0404 – Motor
Rated Power" parameter. This change
will affect P0410.
Press the
16
If necessary, change "P0402 – Motor
Rated Speed". This change will affect
P0122 to P0131, P0133, P0134, P0135,
P0182, P0208, P0288 and P0289.
Press the
18
If necessary, change "P0406 – Motor
Ventilation" parameter.
Press the
The parameters to come after selecting
P0406 may vary according to the type of
control set at P0202.
20
Press the BACK /ESC key to end the
oriented start-up routine.
Press the BACK/ESC again to go back to
the monitoring mode.
Figure 5.1: Oriented Start-up
Action/Display Indication
key to the next parameter.
key to the next parameter.
key to the next parameter.
key to the next parameter.