Description of the device
Note!
Ensure the correct connection of the device to the facility system.
–
For the Levelcontrol make-up variant in particular, the signal line from the level sensor of the pressure
maintenance station must be connected to the device. Connection takes place via LIS.
–
If in Levelcontrol operating mode, no signal line can be connected from the level sensor to the pressure
maintenance station, make-up can be performed manually via the NSP button on the device, see chapter 9.3
"Manual make-up" on page 23 .
4.4
Scope of delivery
The scope of delivery is described in the shipping document for the initial shipment and the content is shown on the packaging.
Immediately after receipt of the goods, please check the shipment for completeness and damage. Please notify us immediately of
any transport damage.
Basic degassing equipment:
•
Device
•
3 ball valves for degassing and makeup connections
•
Operating manual
4.5
Optional equipment and accessories
The following optional equipment and accessories are available for this device:
•
Fillset for make-up with water.
–
Fillset with integrated backflow preventer, water meter, dirt trap, and locking mechanisms for the "WC" make-up line.
•
Fillset Impulse with FQIRA+ contact water meter for make-up with water.
–
If the Fillset Impulse with FQIRA+ contact water meter is installed in the make-up line, you can regulate the entire
make-up quantity and the soft water capacity of Fillsoft softening systems. The operational reliability of the device is
assured and prevents automatic make-up during major water loss or small leaks.
•
RS-485 port
–
Use this port to retrieve all controller data and to enable the communication with control centres or other devices.
The following interfaces can be operated via the RS-485 port:
•
Reflex I/O modules
•
Ethernet
•
Modbus RTU
Other modules upon request
Note!
If required, please contact Reflex Customer Service for details of the connections and information about the
accessories offered.
•
Fillsoft for softening the make-up water from the potable water supply system.
–
Fillsoft is installed between Fillset and the device. The device controller evaluates the make-up quantities and signals
the required replacement of the softening cartridges.
•
Reflexomat for systems with pressure maintenance stations.
–
The combination of Reflexomat and device should be given preference In spite of a degassed network, the Reflexomat
ensures extremely flexible operation at constant pressure. Make-up is executed depending on the water level
measured with the "LIS" level sensor of the Reflexomat in the expansion vessel of the pressure maintenance station.
For a make-up request, the Reflexomat controller activates a 230 V signal to the device controller.
•
Gas discharge measurement for optimised degassing operation.
Note!
Separate installation, operation, and maintenance instructions are supplied with the accessories and optional
equipment.
10 — English
•
Reflex Control Remote for remote maintenance by Reflex
Service via the Reflex Remote Portal with intuitive user
interface
Vacuum spray degassing — 20.05.2019