ERR
Error/message
code
14
Discharge period
19
Continuous stop > 4 h
21
Maintenance
recommended
20
Make-up
quantity/quantity
exceeded
24
Softening/desalination
9.5
Reset
Guidance through the reset can be provided via the Reflex Control Smart app and must then be confirmed by pressing the Auto
button when requested.
You can perform a reset it there is a need to reset the system to factory settings.
1.
Ensure that the system is in stop mode.
2.
Simultaneously press the Auto button and the Stop button for longer than 5 seconds. All LEDs flash briefly.
3.
Release the stop and auto buttons again.
The reset is performed and the device commences the start routine.
Note!
After the reset, the continuous degassing and interval degassing operating times are automatically synchronised from
this new point in time, see chapter 8.1.1 "Automatic mode" on page 21 .
Cause
1.
Degassing line closed.
2.
Dirt trap clogged.
1.
The system has been in stop
mode for more than 4 hours.
1.
Service interval time
exceeded.
1.
Set value exceeded
1.
Soft water capacity too low.
2.
Conductivity of the fluid is
too high
3.
Maximum operating
duration has been exceeded.
Vacuum spray degassing — 20.05.2019
Reaction
1.
Open the degassing
line.
2.
Clean the dirt trap.
•
Set the controller to
automatic mode – by
pressing the Auto-
button on the system.
•
Arrange for a service to
be performed.
•
Reset the set value.
•
Check the system for
leaks.
•
Check the make-up
tank filling level
•
Reset the counter.
1.
Replace softening
cartridge (Fillsoft).
2.
Replace softening
cartridge (Fillsoft Zero).
3.
Perform service and
reset the counter
Controller
Foil
LED no.
/ f [Hz]
✔
06 / 100 Hz
01 / 0.5 Hz
✔
06 / 100 Hz
05 / 0.5 Hz
✔
06 / 100 Hz
07 / 0.5 Hz
✔
05 / 0.5 Hz
01 / 5 Hz
English — 25