5
Technical data
Note!
The following values apply for all systems:
–
Permissible flow temperature:
–
Permissible operating temperature make-up degassing:
–
Permissible ambient temperature:
–
Permissible operating gauge pressure:
–
Maximum inlet pressure for make-up:
–
Make-up capacity:
–
Separation level, dissolved gases:
–
Separation level, free gases:
–
Degree of protection:
5.1
Electrical system
Type
Power output
(kW)
Servitec S
0.2
5.2
Dimensions and connections
Type
Weight
(kg)
Servitec S
12.4
5.3
Operation
Type
System volume
(100% water)
(m³)
Servitec S
Standard values for the maximum "Va" system
volume to be degassed under extreme conditions
during commissioning at a nitrogen reduction
from 18 mg/l to 10 mg/l.
1
Continuous degassing "t" [h]
2.
System volume "Va" [m
Power supply
Fusing
(V / Hz)
230 / 50
Height
Width
(mm)
(mm)
572
System volume
(50% water 50%
glycol)
(m³)
6
4
3
]
Vacuum spray degassing — 20.05.2019
70° C
0 °C – 30 °C
0 °C – 35 °C
8 bar
6 bar
0.05 m³/h
≤ 90 %
100 %
IP 42
Number of
(A)
RS-485
interfaces
10
1 piece as
plug-in
module
Depth
(mm)
340
211
Working
pressure
(bar)
0.5 – 4.5
Technical data
I/O
Electrical voltage
module
control unit
(V, A)
External
230, 4
optional
module
Degassing
Degassing
device
system
connection
connection
Internal
Internal
thread ½ "
thread ½ "
Permissible operating
gauge pressure
(bar)
8
Noise level
(dB)
54
Make-up
connection
Internal
thread ½ "
Operating
temperature
(°C)
0 – 70