Installation
6.4.1

Pressure-dependent "Magcontrol" make-up mode

1
Bladder expansion vessel
2
"WC" make-up line
3
For optional equipment and accessories, see
chapter 4.5 "Optional equipment and accessories" on
page 10
Operating mode "Magcontrol" is set using the Reflex Control smart app. This operating mode is used for facility systems with an
expansion vessel. Water is added dependent on the pressure in the facility system and the set minimum operating pressure p0. The
pressure sensor required for this is integrated in the device. The degassing lines are connected close to the bladder expansion
vessel. This ensures that the pressure monitoring for water make-up is provided.
6.4.2

Level dependent "Levelcontrol" make-up mode

As supplied, the device is preset to "Levelcontrol" operating mode. Changeover to "Magcontrol" as well as regulation of the system
takes place via the app, see chapter 9.1 "Reflex Control Smart" on page 22 .
1
Pressure maintenance station
2
"WC" make-up line
3
For optional equipment and accessories, see
chapter 4.5 "Optional equipment and accessories" on
page 10
16 — English
4
5
6
PIS
4
5
6
PIS
Vacuum spray degassing — 20.05.2019
Device
"DC" degassing line (degassed water)
"DC" degassing line (gas-rich water)
Pressure sensor
Device
"DC" degassing line (degassed water)
"DC" degassing line (gas-rich water)
Pressure sensor