  • ESPAÑOL, página 537
Controller

Error table

Troubleshooting is also described in the app.
ERR
Error/message
code
01
Minimum pressure
(expansion
vessel)
02.1
Insufficient water
02.2
Insufficient water
05
Vacuum error
06
Make-up time
exceeded
07
Make-up
cycles/quantity per
unit time exceeded
08
Pressure
measurement
(expansion vessel)
10
Maximum pressure
24 — English
Cause
1.
Set value P0 not reached
2.
Water loss in the system
3.
Pump fault
4.
Expansion vessel defective
5.
Make-up interrupted – or a
make-up error.
1.
Dirt trap clogged.
2.
Feed pipe blocked.
Vacuum is not generated quickly
enough.
1.
Vacuum pump defective.
2.
Gas in the vacuum pump.
3.
Degassing valve/check valve
at the quick air vent leaking.
4.
Quick air vent dripping
1.
It is not possible to create a
vacuum
2.
A vacuum cannot be
maintained
3.
Pump runtime exceeded
1.
Set time exceeded.
2.
Make-up rate insufficient.
3.
Water loss in the system.
1.
Set value exceeded
1.
Controller receives incorrect
signal
2.
Pressure sensor outputs
values outside the working
range
(4-20 mA)
1.
Set value
Pmax = Psv-0.5 bar
exceeded
Vacuum spray degassing — 20.05.2019
Reaction
1.
Check P0 set value.
2.
-
3.
Arrange for the pump
to be checked.
4.
Check the system's
pressure expansion
vessel.
1.
Clean the dirt trap.
2.
Unblock the feed
pipe/check the make-
up pipe.
1.
Check the pump and
replace as necessary.
2.
Replace the check valve
at the quick air vent.
(ensure consistent
terminology)
3.
4.
Check the water quality
– fluid foaming/oxygen
inhibitor. Water quality
must comply with VDI
2035
1.
Check vacuum pump
2.
Seal the leak in the
system.
3.
Reset pump running
time
1.
Check the set value.
2.
Check feed pipe.
3.
Check system for leaks.
Seal the leak in the
system
Reset the cycle counter
– occurs by
acknowledging the
error
Connect the pressure
sensor - plug
Check the cable for
damage.
Replace the pressure
sensor.
Check the set value
Check the pressure
transducer
Lower the pressure
Check expansion vessel
Foil
LED no.
/ f [Hz]
06 / 100 Hz
02 / 5 Hz
03 / 5Hz
06 / 100 Hz
02 / 8 Hz
07 / 8 Hz.
06 / 100 Hz
02 / 0.5 Hz
06 / 100 Hz
07 / 0.5 Hz
01 / 0.5 Hz
06 / 100 Hz
07 / 0.5 Hz
06 / 0.5 Hz
06 / 5 Hz
02 / 5 Hz
03 / 5Hz

Publicidad