5 Mounting

5
Mounting
5.1

Requirements for Mounting

Requirements for the Mounting Location:
Danger to life due to fire or explosion
Despite careful construction, electrical devices can cause fires.
• Do not mount the product in areas containing highly flammable materials or gases.
• Do not mount the product in potentially explosive atmospheres.
☐ The mounting location must be suitable for the weight and dimensions of the inverter (see
Section 10 "Technical Data", page 56).
☐ The mounting location should be freely and safely accessible at all times without the need for
any auxiliary equipment (such as scaffolding or lifting platforms). Non-fulfillment of these
criteria may restrict servicing.
☐ The inverter can be mounted in a position that is directly exposed to solar irradiation. There is,
however, the possibility that the inverter reduces its power output to avoid overheating due to
high temperatures.
☐ The DC load-break switch of the inverter must always be freely accessible.
☐ Climatic conditions must be met (see Section 10 "Technical Data", page 56).