7 Commissioning
Procedure:
1. Position the enclosure lid of the AC connection unit
on the AC connection unit and first tighten the
upper-left and lower-right screws, and then the
remaining screws crosswise using a Torx screwdriver
(TX 25) (torque: 6 Nm (53 in-lb)).
2. Position the enclosure lid of the DC connection unit
on the DC connection unit and first tighten the
upper-left and lower-right screws, and then the
remaining screws crosswise using a Torx screwdriver
(TX 25) (torque: 6 Nm (53 in-lb)).
3. Turn the DC load-break switch of the inverter to
position I. To do so, first remove the padlock.