Section 4: Other Programming; Program Zones And Partitions; Enable Rf5132 Supervision - DSC RF5132-433 Manual De Instrucciones

Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

4.1 Program Zones and Partitions

Now that you have enrolled the wireless devices, you should complete all zone programming on the system. Although
the exact programming required varies depending on which control panel the RF5132 is connected to, you should
check that the following programming areas are completed correctly for each wireless zone:
• Enable zones and/or assign zones to one or more partitions (programming sections [202]-[205] or [202] to [265]
for the PC5020/PC1616/PC1832/PC1864).
• Program the definition for each zone (programming sections [001]-[004]).
• Enable the wireless zone attribute for each wireless zone (PC580, PC1555, PC1616, PC1832, PC1864, PC501X
v2.0, PC5020 v3.0 and higher only) (sections [101]-[132]).
See your system Installation Manual, for more information on each of the above programming sections.

4.2 Enable RF5132 Supervision

The control panel will supervise the RF5132 receiver via the Keybus after at least one device has been enrolled on the
module (see section 3.2 "Enrolling Wireless Devices").
To activate module supervision, after you enroll the first device(s):
1. Exit and then re-enter installer's programming.
2. Enter programming section [902], wait approximately 1 minute.
3. To exit press [#].
The system will generate a General System Supervisory trouble if the module is removed from the Keybus. If you need
to remove the RF5132 module from an existing system, you will have to disable supervision of the RF5132.
NOTE: Deleting all devices from the RF5132 or defaulting the RF5132 will cause a supervisory fault.
To disable RF5132 supervision:
1. Disconnect the RF5132 from the Keybus.
2. Enter [*][8][Installer Code].
3. Enter [902]. The control panel will clear all supervision and re-scan the system for connected modules. The scan
will take approximately one minute.
4. To exit press [#].
To review which modules the control panel is currently supervising:
1. Enter [*][8][Installer's Code].
2. Enter [903] to display all modules. On a LED 32 zone keypad, light [17] will indicate that the RF5132 is present
on the system. On LCD keypads, scroll until the module name appears on the display.
3. To exit press [#].
If the RF5132 module does not show on the keypad, one of the following conditions may be present:
• the module is not connected properly to the Keybus
• there is a problem with the Keybus wiring run
• the module does not have enough power
• no devices have been enrolled on the RF5132

Section 4: Other Programming

9

Hide quick links:

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Rf5132-868Power seriePowerseries rf5132-868

Tabla de contenido