Operation And Faults - S&P UTBS Serie Instrucciones De Uso

Ocultar thumbs Ver también para UTBS Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

Firstly, enter programming mode. The inverter has two operating modes, RUN and PRO-
GRAMMING. To move from one to the other, press ESC for two seconds.
Location of the 3 Mode Leds. Depending on how
they are lit up, they indicate the selected mode:
- SEQUENTIALLY: Run mode
- SIMULTANEOUSLY: Programming mode
• Press ESC for two seconds until the mode indicator LEDs flash simultaneously.
Next unlock the inverter:
• Press "ENT" and turn the wheel until you reach the "SUP-" menu
• Press "ENT" and turn the wheel until you reach the "COD" parameter
• Press "ENT" and turn the wheel until "1951" appears
• Press "ENT" and turn the wheel until "OFF" appears
• Press "ENT" and return to the main menu by pressing "ESC" twice
Check if the value of the "tFr" parameter on the "drC" menu is greater than or equal to the
value of the equipment's working point frequency. If it is not, change the parameter to a value
greater than or equal to the equipment's working point:
• Press "ENT" and turn the wheel until you reach the "drC-" menu
• Press "ENT" and turn the wheel until you reach the "tFr" parameter
• Press "ENT" and turn the wheel until the value is greater than or equal to the equipment's
working point frequency
• Press "ENT" and return to the main menu by pressing "ESC" twice
Then, enter the value of the equipment working point frequency in the "HSP" parameter of
the "Set" menu::
• Turn the wheel until you reach the "Set-"menu
• Press "ENT" and turn the wheel until you reach the "HSP" parameter
• Press "ENT" and turn the wheel until the value of the equipment working frequency
has been entered
• Press "ENT" and exit the configuration menu by pressing "ESC" three times
Finally, again press "ESC" for two seconds until the 3 indicator LEDs light sequentially to return
to RUN mode (automatic frequency converter operation mode).

6.7.2.3.2 OPEraTION aND faUlTs

starting up the equipment:
The equipment starts up automatically when the power supply is connected. The value of the
set point can be changed using the rPI parameter, which can be accessed from the "rEF",
"Set" menus and the "-PI" submenu of the "Fun" menu.
55

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Utbs-2Utbs-3Utbs-5Utbs-8

Tabla de contenido