Power Supply Wiring - Mitsubishi Electric CITY MULTI PLFY-P NFMU-E Serie Manual De Instalación

Ocultar thumbs Ver también para CITY MULTI PLFY-P NFMU-E Serie:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

4. Electrical work
A
B
~208/230V
A
~208/230V
Fig. 4-7
Total operating current of the indoor
unit
*1 The Ground-fault interrupter should support inverter circuit.
The Ground-fault interrupter should combine using of local switch or wiring breaker.
Indoor unit
PLFY-NEMU, PMFY-NBMU, PEFY-NMSU,
Type 1
PCFY-NKMU, PKFY-NHMU, PKFY-NKMU, PLFY-NFMU
Type 2
PEFY-NMAU
Type 3
PEFY-NMHSU
Others
Other indoor unit
Please pick up "C" from the tripping characteristic of the breaker.
<Example of "F2" calculation>
= 14.65
*3 Current sensitivity is calculated using the following formula.
G1
Current sensitivity
Wire thickness
2
1.5 mm
, AWG14
2
2.5 mm
, AWG13
2
, AWG11
D
C
C
C
C
C
B
D
C
L1 L2
M1 M2
S
1 2
TB2
TB5
TB15
Minimum wire thickness (mm², AWG.No)
Main cable
Branch
1.5, AWG14
1.5, AWG14
1.5, AWG14
2.5, AWG13
2.5, AWG13
2.5, AWG13
V1
V3
56
66

4.2. Power supply wiring

IEC57, 245 IEC 53 or 227 IEC 53.
provided by the air conditioner installation.
[Fig. 4-7]
A
Ground-fault interrupter
B
C
Indoor unit
D
Pull box
Warning:
Never splice the power cable or the indoor-outdoor connection cable,
otherwise it may result in a smoke, a fire or communication failure.
Ground-fault interrupter *1
Ground
V2
2.4
1.6
Local switch (A)
Breaker for wiring
(NFB)
Capacity
Fuse
16
16
25
25
32
32
Sample chart
6000
600
SAMPLE
60
10
1
1
2
3
4
6
8
C
Rated Tripping current (x)
10
20

Publicidad

Tabla de contenido
loading

Tabla de contenido