Flashes 5 ×
Cause
The Open power limit has been activated.
The door system has stopped in the door
Open direction.
Remedy
Remove the triggering obstacle.
If the door system stopped before the
Open end-of-travel position without a
discernible reason:
Check the door mechanics or the
tension of the toothed belt.
Or
Acknow-
Give an impulse via
ledgement
The door closes.
LED
Flashes 6 ×
Cause
System error/malfunction in operator
system
Remedy
Delete the door data if required (see
section 11.2). Then teach in the door
system again (see section 5.1).
If the operator error occurs again:
Replace the operator.
Acknow-
Give an impulse via
ledgement
The door opens (reference run).
LED
Flashes 7 ×
Cause
The operator has not been taught in (no
error, only a notification).
Remedy /
Provide an impulse and initiate a
acknow-
learning run by
ledgement
The door closes.
LED
Flashes 8 ×
Cause
The operator does not have a reference
point (no error, only a notification)
Remedy /
Provide an impulse and initiate a
acknow-
reference run by
ledgement
The door opens.
Note
Normal behaviour following a power
failure, if
no door data is available,
the door data has been deleted,
the last door position is not known.
82
Delete the door data if required
(see section 11.2). Then teach in
the door system again (see
section 5.1).
Readjust the tension of the
toothed belt (see section 9.1).
an external button,
a hand transmitter button,
the T button.
an external button,
a hand transmitter button,
the T button.
an external button,
a hand transmitter button,
the T button.
an external button,
a hand transmitter button,
the T button.
TR10K009 RE / 02.2016