Installation • Centrifugal Pump Suction Connection
No support or
uneven mounting
not recommended.
Suction pipe sloping downward to pump inlet will
trap air which will reduce performance and may
cause pump to lose prime.
Suction piping that is undersized will create excess
friction losses that may cause cavitation and a
reduction in pump performance.
Excess fittings and bends in suction line results in
trapped air, reduced performance, and high friction
losses which may cause cavitation.
Suction entrapment hazard if strainer is
not used.
Not Recommended
See Pages 10 and 11 for
Swimming Pool Installation requirements.
Do not use
Concentric
Reducer.
Excess use of pipe fittings
means potential air leaks.
Elbow immediately in
front of pump intake
not recommended.
Concentric Reducer causes high spots
along the suction line resulting in air pockets.
Do not install valves
in suction line.
Long run
not recommended
Pipe diameter
("D") undersized
reduces performance
Vortex caused by
insufficient submergence
may cause pump to
lose prime.
No strainer
may cause
pump to
clog.
Unsupported
pipe causes
excessive stress
on pump and fittings.
High suction
lift should
be avoided.
Less than
4 x "D"
Insufficient bottom
clearance