Parker Hiross Hyperchill ICE150 Manual De Uso página 15

Ocultar thumbs Ver también para Hyperchill ICE150:
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

4.4.1.2
Alarm relay management
0
Relay normally deactivated, excited by an alarm.
Relay normally excited (also with control OFF), deactivated
1
by an alarm.
Relay normally excited (only with control ON), deactivated
2
by an alarm or with control OFF.
4.4.2
Temperature control
PARAMETER
CODE
SEt
Temperature control set point
dIF
Temperature control differential
LI5
Set point lower limit
4.4.3
B1 sensor parameters
PARAMETER
CODE
cHAI
High temperature confi guration
HAI
High temperature alarm
LAI
Low temperature alarm
CAI
Sensor calibration
Low temperature alarm reset
dbI
differential
4.4.4
B2 sensor parameters
PARAMETER
CODE
cHA2
High temperature confi guration
HA2
High temperature alarm
LA2
Low temperature alarm
CA2
Sensor calibration
Ab2
B2 sensor presence
4.4.5
B3 sensors parameters
PARAMETER
CODE
HA3
High temperature alarm
LA3
Low temperature alarm
CA3
Sensor calibration
4.4.6
B5 sensors parameters
PARAMETER
CODE
HA5
High temperature alarm
LA5
Low temperature alarm
CA5
Sensor calibration
English
4.4.7
B7 sensor parameters
PARAMETER
High temperature confi guration
High temperature alarm
Low temperature alarm
Sensor calibration
B7 sensor presence
TYPE
DEFAULT
4.4.8
Compressor parameters
--
D
PARAMETER
4.0
D
Compressor rotation
5.0
U
Compressor 1 operation hour
counter
TYPE
DEFAULT
Compressor 3 operation hour
0
U
counter
60.0
Compressor 2 operation hour
D
counter
-20.0
D
Compressor 4 operation hour
0.0
U
counter
1.0
Compressor 1 hour counter
U
threshold
Compressor 3 hour counter
threshold
TYPE
DEFAULT
Compressor 2 hour counter
0
U
threshold
60.0
U
Compressor 4 hour counter
3.0
U
threshold
0.0
4.4.9
Pump parameters
U
1.0
U
PARAMETER
Pump stop delay
TYPE
DEFAULT
Pump start delay
60.0
4.4.10
Antifreeze heater parameters
U
-20.0
U
PARAMETER
0.0
Set point adjustment (B1)
U
Temperature control differential (B1)
TYPE
DEFAULT
Antifreeze heater operating mode
(see para. 4.4.8.1)
60.0
U
Antifreeze heater activation mode
-20.0
U
(see para. 4.4.8.2)
0.0
U
Activation set point (B3)
CODE
TYPE
DEFAULT
cHA7
0
U
HA7
60.0
U
LA7
3.0
U
CA7
0.0
U
Ab7
1.0
U
CODE
TYPE
DEFAULT
rot
2
U
D
HI
-
D
H3
-
D
H2
-
D
H4
-
tHI
0
U
tH3
0
U
tH2
0
U
tH4
0
U
CODE
TYPE
DEFAULT
dP5
5
U
dPA
5
U
CODE
TYPE
DEFAULT
SEA
7.0
U
dIA
1.0
U
FUA
0
U
AbrA
2
U
ArA
5.0
U
ICE150-230
4.4.10.1 FUA antifreeze heater operating mode
Temperature control by B1, activation by B3 (ambient
0
temperature sensor)
Temperature control by B3 (ambient temp. sensor) with
1
ARA set point.
4.4.10.2 AbrA antifreeze heater activation mode
0
Activation only when controller is 'On'
1
Activation also when controller is 'Off'
Activation also when controller is 'Off'. During heater opera-
2
tion the pump is activated.
4.5 Parameter management
4.5.1
Temperature setting (see fi g.1)
1. 1. Turn the main swicth (QS) to "ON" and wait for the temperature
visualization.
2. Press buttons "P3" and "P5" together, to enter into "dIrE" (D)
parameters.
3. Press button "P4" to select "SEt" parameter, press the button
"P5" to confi rm.
4. Change the value, using the up and down arrow buttons "P3" and
"P4", then press button "P5" to confi rm.
6. Press the button "P3" to return on "dIrE" parameter.
7. Press the button "P5" to exit.
4.5.2
Differential setting (see fi g.1)
1. Turn the main swicth (QS) to "ON" and wait for the temperature
visualization.
2. Press buttons "P3" e "P5" together, to enter into "dIrE" (D)
parameters.
3. Press button two times "P4" to select "diF" parameter, press the
button "P5" to confi rm.
4. Change the value, using the up and down arrow buttons "P3" and
"P4", then press button "P5" to confi rm.
6. Press the button two times "P3" to return on "dIrE" parameter.
7. Press the button "P5" to exit.
4.5.3
Visualization sensors B1,B2...
"B1" is the "set" sensor of the macchine.
1. Start the chiller.
2. Press the button "P4" to visualize the temperature of the next sen-
sor.
3. Press the button "P5" to visualize the sensors "b01" .."b02"....
It is recommended to leave on the display the B1 "set" sensor.
5/8

Publicidad