Installation and User Manual SAGA ELECTRO
3.8 Door switch
The door switch refers to the switch on the sauna door. This switch complies with the regulations laid down in
Section 22.100 of the standard EN 60335 2-53. Public and private saunas, i.e. saunas where the heater can be
switched on from outside the sauna or by using a timer, must have a door switch.
T2
Image. 8 Door switch
3.9 Installing the sensor near a supply air vent
The sauna room air should be exchanged six times in an
hour. The diameter of the supply air pipe should be
between 50 and 100 mm.
A circular air supply vent (360°) must be
installed at least 1000 mm away from the sensor.
An air supply vent with a flow-directing panel
(180°) must be installed at least 500 mm away from
the sensor. Air flow must be directed away from the
sensor.
Contactor
Box
Sensor
Min 300mm
Door switch
Magnet
1000 mm
360°
500 mm
180°
9
Connection box
Max 18 mm
Sensor
Sensor