Software Diagnosis - Aventics DDL Instrucciones De Servicio

Sercos iii
Ocultar thumbs Ver también para DDL:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 145
68
AVENTICS | SERCOS III | R412012613–BDL–001–AC
Appendix

13.6 Software diagnosis

The bus coupler provides diagnostic data:
Detailed information on the structures for diagnosis of the
individual DDL participants can be found in the descriptions of
the respective DDL participants.
Transmitting the diagnosis to the PLC can be inhibited by using
the S1.1 DIP switch.
S1.1 to 0
The diagnostic data will not be sent to the PLC (default).
S1.1 to 1
The diagnostic data will be sent to the PLC.
As an aid, the following errors and warnings in the
IDN/S-0-0390 or S-0-1500.0.32 will be reported:
W
IDN/0390:
– CP2: Address gap/missing slave:
A001 error (subbus slave missing)
– CP2: Configuration error = no slave present:
A030 error (subbus configuration error)
– CP4: Address gap/missing slave:
A001 warning (subbus slave missing)
– CP4: Diagnosis is available for DDL participant:
A010 warning (device errors)
Table 13:
S-0-1500.0.32
1)
Diagnostic bit
Status code
Bit 0 (24 V elec.)
0x3100
Bit 1 (24 V valve) 0x3400
Bit 2 (EP safety
0x2300
cut-off)
Bit 2 (others,
0xA010
e.g. 24 V valve)
Bit 7
0xA020
(DDL comm.)
1)
See bit description in the respective DDL participant documentation
Status code
Description
Mains voltage
Supply voltage
Current on the device output side
Device errors
Communication errors

Publicidad

Tabla de contenido
loading

Tabla de contenido