S8910U3000
• Igniter current draw at 132 Vac must not
exceed 5A.
Sensor:
Separate sensor required for remote sensing applications.
Wiring:
Use existing appliance wiring. If repair or replacement of lead-
wires is required, follow instructions on appliance label.
Use included quick connect terminals and wiring adaptors
according to instructions.
Prepurge:
32 seconds.
Igniter Warmup:
7 (12), 17 (27), 34 or 45 seconds. Numbers in parenthesis
represent second and third trial for ignition timings.
Purge between Trials for Ignition:
96 seconds (32 second prepurge and 64 seconds interpurge).
Flame Failure Response Time:
1.5 seconds maximum.
Ignition Sequence:
The number of trials for ignition and trial time are determined
by selectable DIP switches.
Ambient Operating Temperature:
-40 to +175 °F (-40 to +79 °C).
Accessory Kit (Included):
• White-Rodgers adapter.
• Robertshaw ground lead.
• Four 1/4 in. female .032 quick-connects.
ORDERING INFORMATION
When purchasing replacement and modernization products from your TRADELINE® wholesaler or distributor, refer to the
TRADELINE® Catalog or price sheets for complete ordering number. If you have additional questions, need further information,
or would like to comment on our products or services, please write or phone:
1. Your local Honeywell Environmental and Combustion Controls Sales Office (check white pages of your phone directory).
2. Honeywell Customer Care
1985 Douglas Drive North
Minneapolis, Minnesota 55422-4386
3. http://customer.honeywell.com or http://customer.honeywell.ca
International Sales and Service Offices in all principal cities of the world. Manufacturing in Belgium, Canada, China, Czech
Republic, Germany, Hungary, Italy, Mexico, Netherlands, United Kingdom, and United States.
34-00008EFS—01
• One 3/16 in. female .032 quick-connect.
• Nine wire labels.
Approvals:
IAS Design Certified: Certification Report No. C2027002.
IMPORTANT
The specifications given in this publication do not
include normal manufacturing tolerances. Therefore,
this unit may not exactly match the listed specifica-
tions. Also, this product is tested and calibrated
under closely controlled conditions, and some minor
differences in performance can be expected if those
conditions are changed.
The S8910U package contains the S8910U control, and easy-
to-use instructions, plus the accessories required to adapt the
existing hot surface ignition module. The accessory bag
assembly includes the White-Rodgers adapter, Robertshaw
ground lead, four 1/4 in. female .032 quick-connects, one 3/16
in. female .032 quick-connects, and nine wiring labels. The
wiring labels are included to assure proper marking of the
wires attached to the existing module.
A complete listing of the specific Honeywell and other
modules that the S8910U is designed to replace is provided in
Tables 1 through 3.
NOTE: The S8910U is intended to replace only defective
ignition controls. The service technician should
make sure that the other parts of the appliance
and control system operate safely and reliably
before replacing the ignition control.
Model Available:
S8910U Universal Hot Surface Ignition Module.
2