Input Voltage:
Supply Tolerances:
Output Voltage:
Output Distortion:
Output Current:
Output Power:
Input Connection:
Output Connection:
Protection:
Operating Range:
Storage Range:
Environmental:
Safety:
EMC:
Size:
Weight:
2
Factory set to 230V, 115V or 100V; 50Hz or 60Hz.
Installation Category II.
230V setting : 198V – 253V
115V setting:
99V – 127V
100V setting:
90V – 110V
50Hz setting: ± 0·5Hz
60Hz setting: ± 0·6Hz
Tracks the amplitude of the fundamental of the input voltage. A variable
voltage input may be used to adjust the output voltage to within the limits
specified by EN61000–3–2.
Dependent on the purity of the input but will generally meet the requirements
of EN61000–3–2.
Maximum continuous output current is 4·4A.
Maximum peak current (repetitive or surge) is 10A
Maximum output power is input voltage x 4·4 VA
IEC connector; front panel switch.
U.K., Schuko, or other national outlet sockets. Load power switch can be set
to DIRECT or CORRECTED for 'A–B' comparisons.
Thermal trip automatically diverts load to a DIRECT connection in the event of
thermal overload.
+5°C to +35°C at full rated output; 20% to 80% RH (non-condensing).
–40°C to +70°C
Indoor use at altitudes to 2000m, Pollution Degree 2.
Complies with EN61010–1
Complies with EN61326-1.
307 x 105 x 225 mm (W x H x D)
5 kg.
Specification