Setting Gas/Air Regulation - Rotex GW-30 C22 Instrucciones De Instalación

Ocultar thumbs Ver también para GW-30 C22:
Tabla de contenido

Publicidad

Idiomas disponibles
  • ES

Idiomas disponibles

  • ESPAÑOL, página 270
7.8

Setting gas/air regulation

The CO
setting has been set at the factory and does not require any adjustments, in principle.
2
The setting can be checked by measuring the CO
of any disturbance of the setting, the replacement of the gas valve or the conversion to a different
type of gas must be checked, and if necessary set in accordance with the following instructions.
Always check the CO
percentage when the lid is open.
2
Checking the carbon dioxide setting
1 Switch off the heat pump module with the user interface.
2 Switch off the gas boiler with the
3 Remove the front panel from the gas boiler.
4 Remove the sample point (a) and enter an appropriate chimney analysis probe.
IMPORTANT
Ensure the start-up procedure of the analysis machine has been
completed before inserting the probe in the sample point.
IMPORTANT
Wait for the gas boiler to run stable. Faulty measurements may
occur if the measuring probe is connected before the boiler is
running stable.
5 Switch on the gas boiler with the
6 Select the High setting by twice pressing the
capital letter "H" will appear on the service display. The user display will show a Busy
symbol. Do NOT carry out a test when a small letter "h" is shown. If this is the case,
press
and
again.
7 Allow the display values to stabilize. Wait at least 3 minutes and compare the CO
percentage to the values in the following table.
CO
value at
2
maximum power
Maximum value
Minimum value
8 Note the CO
percentage at maximum power. This is important in relation to the following
2
steps.
IMPORTANT
It is NOT possible to adjust the CO
carried out. If the CO
contact your local service department.
9 Select the Low setting by once pressing the
"L" appears on the service display. The user display will show a Busy symbol.
10 Allow the display values to stabilize. Wait at least 3 minutes and compare the CO
percentage to the values in the following table.
CO
value at
2
minimum power
Maximum value
Minimum value
(a) CO
value at maximum power registered at setting High.
2
percentage in the combustion gases. In case
2
-
button.
appears on the service display.
button and create a request for space heating.
and
buttons simultaneously. A
Natural gas G20
Propane G31 (30/37/50 mbar)
9.6
8.4
percentage when the test program is being
2
percentage deviates from the values in the above table,
2
and
buttons simultaneously.
Natural gas G20
Propane G31 (30/37/50 mbar)
(a)
8.4
2
10.8
9.8
2
9.4
44

Publicidad

Tabla de contenido
loading

Este manual también es adecuado para:

Gw-30 c28Gw-30 c33Rkombg22aav1Rkombg28aav1Rkombg33aav1

Tabla de contenido