11 If the CO
percentage at maximum and minimum power is within the reach stated in
2
the above tables, the CO
setting of the boiler is correct. If NOT, adjust the CO
2
setting in accordance with the instruction in the following chapter.
12 Switch off the unit by pressing the
position. Make sure it is gas tight.
13 Return the front panel to its place.
CAUTION
Work on gas carrying parts may ONLY be carried out by
qualified, competent individuals.
Adjusting the carbon dioxide setting
IMPORTANT
Only adjust the CO
sure the adjustment is necessary. No adjustments may be made to the gas
valve without prior permission from your
local Rotex distributor. In Belgium, the gas valve may NOT be adjusted and/or
the seal may NOT be removed or broken. Contact your distributor.
1 Remove the cap (A) which covers the adjuster screw.
2 Turn the screw (B) to the right to increase the CO
decrease it. See the following table for the desired value.
Measured value at
Set values CO
maximum power
Natural gas 2H (G20, 20 mbar)
10.8
10.6
10.4
10.2
10
9.8
9.6
9.4
9.2
9.0
8.8
8.6
3 After measuring the CO
percentage and adjusting the setting, replace the cover
2
cap and the sample point. Make sure they are gas tight.
4 Select the High setting by twice pressing the
A capital letter will appear on the service display.
5 Measure the CO
percentage. If the CO
2
values in the table which indicates the CO
contact your local distributor.
6 Press + and - simultaneously to leave the test program.
7 Return the front panel to its place.
button and return the sample point to its
setting when you have first checked it and you have made
2
percentage, and to the left to
2
(%) at minimum power (front lid open)
2
Propane 3P
(G31,30/50/37 mbar)
-
9.0±0.1
8.9±0.1
8.8±0.1
8.7±0.1
8.6±0.1
8.5±0.1
and buttons
percentage still deviates from the
2
percentage at maximum power,
2
2
10.5±0.1
10.3±0.1
10.1±0.1
9.9±0.1
9.8±0.1
9.6±0.1
-
simultaneously.
45