Troubleshooting Guide - Astralpool V-HEAT Serie Manual De Instrucciones

Bomba de calor para piscina
Tabla de contenido

Publicidad

Idiomas disponibles

Idiomas disponibles

V-HEAT SERIES · AIR/WATER SYSTEM
The R407C Gas:
⋅ The R407C is a NONFLAMMABLE gas; it has no flash point, and so is not subjected to the rules and regulations of
the transportation of inflammable gases.
⋅ The R407C does not irritate the skin, eyes or mucous membranes and does not produce and side-effects.
⋅ It has a very low level of toxicity for one or many repeated exposures; it does not cause cancer or mutations.
⋅ The R407C may cause freezing if it comes into contact with the skin, due to its immediate evaporation.
⋅ As with all hydrocarbons, whether they are halogenated or not, the R407C gas may, although it has a very low level
of toxicity, cause anaesthetic or preanaesthetic conditions if inhaled deeply and within a closed area.

10 TROUBLESHOOTING GUIDE.

The reasons why your heat pump may not function properly are mentioned below:
The unit does not start:
Operating switch tripped: Check there is no short circuit in the control panel, repair the possible short circuit.
Coil contactor does not activate: Verify that it is not burned, and replace it if it is. Verify the terminals which activate
the coil.
Thermal switch tripped: Verify the voltage of the line. Verify that the operating conditions are correct. Excessive
compressor consumption. Short circuit in the compressor.
Low pressure switch tripped: Verify that the pressure switch operates correctly and substitute if necessary. Verify that
the fan is operating correctly. Verify the refrigerant charge of the equipment (refrigerant leak, loss of refrigerant fluids)
in order to solve this problem; please refer to the refrigerant charge section.
Verify that there is sufficient ventilation around coils. Check for any obstruction of the cooling circuit and eliminate the
obstruction if necessary. Verify that the thermostatic valve is operating properly, checking the bulb has no gas leaks
and that the pressure inlet is free of obstruction. Replace if needed.
High pressure switch tripped: Verify that the pressure switch operates correctly and substitute if necessary. Check
the refrigerant charge (excess refrigerant) in order to solve this please refer to the refrigerant charge section. Check
for any obstruction of the cooling circuit and eliminate the obstruction if necessary. Verify there is a good water flow
through the condenser, checking there are no obstructions in the hydraulic circuit, the shut-off valves are open and
the purification pump operates properly (replace if needed).
Flow alarm: Verify the purification pump is operating properly (pump flow may be less than needed). The filter of the
purification pump is dirty. Clean it if needed. By-pass are closed or not sufficiently open. Revise it if needed. The
pump is not working. Revise clock condition and purification mode. The flow switch is faulty (call for service).
Defrost cycle: The ambient conditions are not correct (temperatures are too low). The unit does not work under these
conditions. It is recommended to disconnect the unit.
Low oil level:
Low initial oil charge: Refill up to needed level.
Oil stains on the equipment: Check for leaks in the cooling circuit and repair them if necessary, check the torque on
the high and low pressure valves, and replace them if necessary.
The equipment operates on cycles which are too short:
The low pressure switch opens then closes again: Verify the points mentioned in the "low pressure switch tripped"
section above.
Intermittent contact on machine control unit: Repair or replace the faulty electrical part. Check the temperature
indicator.
⋅ Make sure the equipment is not too large for the facilities.
The equipment does not shut down:
⋅ Verify that the thermostat functions properly, repairing or replacing it if necessary.
Compressor contactor contacts are stuck together: Check that the coil is functioning properly and that the contacts
are not burned.
The pressure of the intake duct is too low: Check the refrigerant charge of the equipment for leaks, to solve this
problem please refer to the refrigerant charge section. Check that there are no obstructions in the cooling circuit,
© ASTRALPOOL 2018. ALL RIGHTS RESERVED. CONFIDENTIAL AND PROPRIETARY DOCUMENT.
ENGLISH
Page 33 of 72

Publicidad

Tabla de contenido
loading

Tabla de contenido