5.3 Initial startup

This section refers to fig.
8
and fig. 9.
The change-over device 185 is always part of a gas dosing
system. The other components of the system determine the
course of commissioning.
Before startup:
1. Open the ball valves (2).
2. For 185-2:
– Ball valves (3) of the bypass lines must be closed.
– Ball valve (4) must be opened.
3. Set operation mode switch (S3) to "man".
4. Set the change-over device to the container battery which
should be used first:
– Open battery 1: Press key (S18) until lamp (H15) lights up.
– Close battery 1: Press key (S22) until lamp (H28) lights up.
– Open battery 2: Press key (S32) until lamp (H29) lights up.
– Close battery 2: Press key (S37) until lamp (H42) lights up.
5. Set operation mode switch (S3) to "auto".

6. Operation

6.1 Control and display elements

6.1.1 Control panel
H15 H28 H29 H42
S18 S22 S32 S37
Fig. 8
Control panel
Pos.
Description
Operation mode switch:
• Manual operation: "man"
S3
• Off: "0"
• Automatic operation: "auto"
Green lamp: Lights up when the valve of container
H15
battery 1 is completely opened.
Red lamp: Lights up when the valve of container
H28
battery 1 is completely closed.
Green lamp: Lights up when the valve of container
H29
battery 2 is completely opened.
Red lamp: Lights up when the valve of container
H42
battery 2 is completely closed.
Key to open the valve of container battery 1 in manual
S18
operation mode.
Key to close the valve of container battery 1 in
S22
manual operation mode.
Key to open the valve of container battery 2 in manual
S32
operation mode.
Key to close the valve of container battery 2 in
S37
manual operation mode.
S3
6.1.2 Change-over device
5
1
185-1
2
185-2
5
2
3
Fig. 9
Control elements of change-over device
Pos.
Description
1
Contact manometer
2
Ball valves of change-over device
3
Ball valves of bypass lines
4
Ball valve of outlet line
5
Motor valve of container battery 1
6
Motor valve of container battery 2

6.2 Operating modes

This section refers to fig. 8.
There are two operation modes which can be selected using
operation mode switch (S3).
6.2.1 Automatic operation mode
Turn switch (S3) to "auto". Operation starts automatically.
6.2.2 Manual operation mode
Turn switch (S3) to "man". Press the respective keys to set the
change-over device to the desired container battery. See section
6.1.1 Control
panel.
The manual operation mode disables the automatic
change-over function. The manual operation mode
Caution
must only be used for commissioning, maintenance
and repairs.
6
2
1
6
2
4
3
11