REQUIREMENT
• When a group control is performed over multiple
refrigerant systems, be sure to turn on the power
supplies to all of the indoor units connected , so that
the address set-up can be completed correctly.
• If turning on the power for each refrigerant system
to set up the addresses, a header indoor unit must
be set for each system. Therefore, an alarm code
"L03" (Duplicated header indoor units) will be
displayed during in operation after the address
setup has been completed. In this case, change the
group address using the wired remote controller so
that only one header indoor unit is set-up.
Address setup procedure 2
Using SW13 and 14 on the interface P.C. board on the outdoor
unit in each system, set up the system address for each system.
(At shipment the address is set to 1 from the factory)
Note) Be careful not to duplicate with any other refrigerant systems
or other line (system) addresses.
Line (System) address switch on outdoor interface P.C. board
SW13
Line
address
1
2
1
2
3
4
5
6
7
8
9
10
11
12
13
14
: Is not used for setup of line address. (Do not change setup.)
Check that the relay connectors between [U1U2] and [U3U4] terminals are come out in all outdoor units to which
the central control is connected. (At shipment from factory: No connection of connector)
Turn on power of indoor/outdoor.
(In order of indoor → → → → → outdoor)
After approx. 1 minute, check that 7-segment display is
U.1.L08 (U.1. flash) on the interface P.C. board.
Push SW15 and start setup the automatic address.
(Max. 10 minutes for 1 line (Usually, approx. 5 minutes))
When the count Auto 1 → Auto 2 → Auto 3 is displayed in
7-segment display section, and it changes from
U. 1. - - - (U. 1. flash) to U. 1. - - - (U. 1. light) , the setup
finished.
Procedure
to
are repeated in other refrigerant systems.
SW14
3
4
1
2
3
×
×
×
×
¡
×
×
×
¡
×
×
×
¡
¡
×
×
¡
×
×
×
¡
¡
×
×
¡
¡
×
×
¡
¡
¡
×
×
×
×
×
¡
×
×
×
¡
×
×
×
×
¡
¡
×
¡
×
×
×
¡
¡
×
×
(Example)
Wire
systematic
diagram
Line
address
4
×
15
×
16
×
17
×
18
×
19
×
20
×
21
×
22
¡
23
¡
24
¡
25
¡
26
¡
27
¡
28
Relay connector
28
Group control over
multiple refrigerant system
Outdoor
Outdoor
Indoor
Indoor
Indoor
Remote
controller
Interface P.C. board
ON
ON
ON
1
2 3 4
1
2 3 4
1
2 3 4
SW11
SW12
SW13
ON
ON
ON
ON
1
2 3 4
1
2 3 4
1
1
SW06
SW07
SW08
SW09
¡
: Switch ON, × : Switch OFF)
(
SW13
1
2
3
4
1
×
×
¡
×
¡
×
¡
¡
¡
×
¡
¡
¡
×
¡
¡
¡
×
¡
¡
¡
×
¡
¡
¡
×
¡
¡
2
U1
U2
For control
wiring between
indoor and
outdoor
Indoor
ON
1
2 3 4
SW14
ON
2 3 4
1 2 3 4
SW10
SW14
2
3
4
¡
¡
¡
¡
¡
¡
×
×
×
×
×
×
¡
×
×
¡
×
×
¡
×
×
¡
×
×
¡
¡
×
¡
¡
×
¡
×
×
×
×
¡
¡
¡
×
¡
¡
×
U3
U4
For wiring of
central control
system